REMEMBER!
To leave the
Programming Mode at
any time, press the
Esc
key. Doing so will
return the CP-220A to
its normal operating
mode. Programming
changes will be stored
automatically.
In
PARAMETER 30,
the descriptive wording used in any or all of the
CP-220A's 8 Line Cards can be turned "OFF" (or back "ON") if desired.
Doing so permits either temporary or permanent suspension of the
customized words on a Line Card-by-Line Card basis.
Programming Procedures:
Through
PARAMETER 30,
each available Line Card can be selected, and its
use of the "Slot English" with which it has been previously programmed (or
copied) can be enabled or disabled.
[SLOT 1 ENGLISH ON] will be displayed and the [1] will be flashing after
entering
PARAMETER 30
. At this time, the descriptive wording used for
any slot can be "turned on" or "turned off," as required.
1.
With the [1] flashing, use the appropriate numeric key (1-8) on the
CP-220A's keypad to select the slot (Line Card) whose English language
programming is to be enabled or disabled.
NOTE: Because the [1] is flashing already, it is not necessary to press
1
to
select Line Card 1.
2. If any changes are necessary, use the
key to move to the [ENGLISH
ON] field. Either [ON] (or [OFF]) will be flashing.
3. Toggling between [ON] and [OFF] can be done with either the
NEXT
or
the
MANUAL/PREVIOUS
keys.
4. Use
either
the or
keys to return to the [SLOT "X"] field. By
repeating the above sequence, any previously performed English
language programming can be selectively enabled or disabled for each
active CP-220A slot.
Default:
The CP-220A has been factory programmed so that all Line Cards have their
English language descriptors "turned on." Thus, as long as these descriptors
have either been programmed or copied in the previous two parameters,
they will automatically be enabled via
PARAMETER 30.
Advancing to Next Parameter:
The next parameter in
Category A
is
PARAMETER 27
and, because it is not
sequential, it cannot be reached with a single press of the
key. To advance
to
PARAMETER 27,
press the
N
key.
The CP-220A displays the parameter just programmed ([PARAMETER
NUMBER 30]) with its first digit flashing, indicating its request for the
desired parameter number. Press either:
•
2
then
7
, or
• the
key
NOTE: When the
is used, the
name
of the next parameter appears
immediately – not its
number
.
CP-220A Central Station Receiver Section 2: Programming the CP-220A Page 2-29
Hook-Up and Installation Manual