6
Assembly Instructions
enCore FC
Operating Instructions
Page 55 of 120
Minimum requirements
If a special setting is required for connecting a specific board or a
specific board channel with a measuring device, you get only the
minimum required settings below the respective connection
diagram.
For details on parameterization refer to the
online help.
6.4.1 General Recommendations for Signal and Data Cable
Signal Connection
The following standard minimum requirements for the used type of cable are
recommended for the signal connection with external transmitters and sen-
sors as well as for the signal connection of external devices:
•
signal cable with a line-to-line capacity smaller than 120 pF/m and
an inductance smaller than 0.7 µH/m
•
Wire diameter greater or equal to 0.5 mm
2
, number of wires accor-
ding to the application, stranded cable, shielded together. Screen at
just one place (preferably on enCore FC) connected with PE.
•
The maximum cable length is dependent on the type of the signal;
refer to the following section for exact specifications.
Data Communication Connection
The following standard minimum requirements for the used type of cable are
recommended for the data communication connection with external sensors
as well as for the data communication connection of external devices accor-
ding to RS232, RS422 or RS485:
•
signal cable with a line-to-line capacity smaller than 120 pF/m and
an inductance smaller than 0.7 µH/m
•
Wire diameter greater or equal to 0.25 mm
2
, number of wires accor-
ding to the application, stranded cable, shielded together. Screen at
just one place (preferably on enCore FC) connected with PE.
Содержание enCore FC1
Страница 7: ...Contents enCore FC Operating Instructions Page 7 of 120 12 Index 118 13 Appendix 120 ...
Страница 121: ......
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 131: ......
Страница 132: ......
Страница 133: ......