Assembly Instructions
6
Page 74 of 120
Operating Instructions
enCore FC
− 2
nd
device in sink mode:
load:
approx. 50 Ω
•
This operating mode can only be used with one transmitter in burst
.
•
max. cable length:
250 m (total)
Hints on parameterization
Branch
<device> – Basic System – I/O boards –
Board <x>: MFE7
Set the following values:
•
channel
A1+ A1−
and
A2+ A2−
: type
HART channel
•
each channel with parameter
Power supply
:
− for device 1: value
On
(source mode)
− for device 2: value
Off
(sink mode)
With this, the operating mode of the channel is set correctly for the
redundant connection of both the HART transmitters with the
ignition protection category EEx d.
19
Burst mode is not supported by all transmitters.
Содержание enCore FC1
Страница 7: ...Contents enCore FC Operating Instructions Page 7 of 120 12 Index 118 13 Appendix 120 ...
Страница 121: ......
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 131: ......
Страница 132: ......
Страница 133: ......