Assembly Instructions
6
Page 82 of 120
Operating Instructions
enCore FC
•
max. cable length depending on the operating mode:
− message, LF or encoder:
500 m
− HF (up to 2 kHz):
250 m
− HF (up to 5 kHz):
100 m
6.4.18 Gas Meter (Turbine): Encoder Index, 2 LF/HF Sensors
(EEx i) via MFE7 Board
Hazardous Area
Safe Area
enCore device
Turbine:
encoder and
2 LF/HF sensors
24V 0V
Isolated pulse
amplifier
(active output)
MFE7 board
D1+
SH
D2+
D3+
GND
12 345 67,8
Fig. 6-23: Interface for turbine meter
encoder index, 2 LF/HF sensors (EEx i) via MFE7
Characteristics MFE7:
•
three galvanically isolated input safe circuits for HF or LF pulse
sensor
•
passive isolated pulse amplifier integrated in the inputs
•
Alternatively, one encoder index or a transmitter can be connected
with frequency interface on channel 3.
Содержание enCore FC1
Страница 7: ...Contents enCore FC Operating Instructions Page 7 of 120 12 Index 118 13 Appendix 120 ...
Страница 121: ......
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 131: ......
Страница 132: ......
Страница 133: ......