Assembly Instructions
6
Page 78 of 120
Operating Instructions
enCore FC
rated voltage:
approx. 21 V
max. load:
300 Ω
− 2
nd
device in sink mode:
load:
approx. 50 Ω
•
max. cable length:
250 m (total)
A HART communicator cannot be used in this operating
mode!
Note that for technical reasons it is not possible to use HART
communicator in a HART loop for diagnostic purposes in this
operating mode.
Hints on parameterization
Branch
<device> – Basic System – I/O boards –
Board <x>: MFE7
Set the following values:
•
channel
A1+ A1−
and
A2+ A2−
: type
HART channel
•
each channel with parameter
Power supply
:
− for device 1: value
On
(source mode)
− for device 2: value
Off
(sink mode)
In folder
<channel>: HART loop <x>
:
•
parameter
Master address
:
− for device 1: value
Primary
− for device 2: value
Secondary
•
For each transmitter, set the parameter
device <x>
to
used
and parameterize all other settings for the individual
transmitters.