6.4.9 HART Measurement Transmitter (EEx d) via MFE7 Board
(without barrier, internal Power Supply)
Hazardous Area
Safe Area
enCore device
MFE7 board
A1+ or A2+
A1− or A2−
SH
HART pressure
transmitter, EEx d
HART temperature
transmitter, EEx d
HART
communicator
+
−
(source mode)
Fig. 6-14: HART pressure and temperature transmitter (EEx d) via MFE7 – example
Characteristics MFE7:
•
a galvanically isolated input safe circuit for a transmitter with HART
interface
•
an active signal and protocol converter integrated in input:
− open-circuit voltage:
approx. 21 V
− voltage at 20 mA:
approx. 12.6 V
− max. load:
600 Ω
− max. 4 transmitters:
thereof max. 1 transmitter in burst mode
11
Up to and including basic system version
03-24
, you could use either up to
4 × transmitters in multidrop mode or 1 × transmitters in burst mode.
12
Burst mode is not supported by all transmitters.