Page 22 of 113
FirePro Xtinguish I&O Manual
V1.05 UL
of abort and maintenance disconnect switches, delay timers, and emergency power shutdown.
Point-to-point wiring schematic diagrams showing all circuit connections to the system control
panel, to the graphic annunciator panel and to external or add-on relays.
Complete calculations to determine the size of backup batteries and method used to determine
number and location of audible and visual indicating devices and number and location of
detectors.
Minimum clearances to combustible materials and the means of egress.
Details of any special features.
Information shall be submitted for approval to the authority having jurisdiction pertaining to the
location and function of:
Detection devices,
Operating devices,
Auxiliary equipment,
Electrical circuitry, if used.
All the apparatus and devices used shall be identified.
Any special features shall be explained.
The as-built installation drawings and the instruction and maintenance manual that includes a full
sequence of operations.
A full set of drawings and calculations shall be maintained on site.
8.1.3
Approval of Plans
Plans and calculations shall be approved prior to installation.
Where field conditions necessitate any change from approved plans, the change shall be approved
prior to implementation.
When such changes from approved plans are made, the working plans shall be updated to accurately
represent the system as installed.
8.2
Enclosure
In the design of a
FirePro
Xtinguish
condensed aerosol total flooding fire extinguishing system, the
integrity of the protected enclosure shall be considered.
The area of non-closable openings in the protected enclosure shall be kept to a minimum.
8.2.1
Loss of Agent
To prevent loss of agent through openings to adjacent hazards or work areas, openings shall be
permanently sealed or equipped with automatic closures.
Where reasonable confinement of agent is not practicable, protection shall be expanded to include
the adjacent connected hazards or work areas or additional agent shall be introduced into the
protected enclosure using an extended discharge configuration.
Forced-air ventilating systems shall be shut down or closed automatically where their continued
operation would adversely affect the performance of the fire extinguishing system or result in
propagation of the fire.
Completely self-contained recirculation ventilation systems shall not be required to be shut down.
The volume of the ventilation system and associated ductwork shall be considered as part of the total
hazard volume when determining the quantity of agent.
The protected enclosure shall have the structural strength and integrity necessary to contain the
Содержание FirePro Xtinguish
Страница 35: ...Page 35 of 113 FirePro Xtinguish I O Manual V1 05 UL...
Страница 36: ...Page 36 of 113 FirePro Xtinguish I O Manual V1 05 UL...
Страница 71: ...18 Appendix C FirePro Xtinguish Generator Datasheets...
Страница 72: ...Page 72 of 113 FirePro Xtinguish I O Manual V1 05 UL...
Страница 90: ...19 Appendix D FirePro Xtinguish Generator Drawings Xtinguish FNX 20S...
Страница 91: ...Page 91 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 20T...
Страница 92: ...Page 92 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 40S...
Страница 93: ...Page 93 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 80S...
Страница 94: ...Page 94 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 40T FNX 80T...
Страница 95: ...Page 95 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 40T FNX 80T...
Страница 96: ...Page 96 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 100S ELECTRICAL ACTUATOR...
Страница 97: ...Page 97 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 200S ELECTRICAL ACTUATOR...
Страница 98: ...Page 98 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 500S ELECTRICAL ACTUATOR...
Страница 99: ...Page 99 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 100S FNX 200S FNX 500S...
Страница 100: ...Page 100 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 1200 FNX 1200S...
Страница 101: ...Page 101 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 1200T FNX 1200TS...
Страница 102: ...Page 102 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 2000 FNX 2000S...
Страница 103: ...Page 103 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 2000T FNX 2000TS...
Страница 104: ...Page 104 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 3000 FNX 3000S...
Страница 105: ...Page 105 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 3000T FNX 3000TS...
Страница 106: ...Page 106 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 4200T FNX 4200TS...
Страница 107: ...Page 107 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 5700 FNX 5700S...
Страница 108: ...Page 108 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 5700T FNX 5700TS...