Page 27 of 113
FirePro Xtinguish I&O Manual
V1.05 UL
9
Condensed Aerosol Fire Extinguishing System Arrangement
The
FirePro
Xtinguish
condensed aerosol generators and ancillary system components shall be
arranged to allow easy inspection and maintenance activities, minimizing the interruption of
protection.
FirePro
Xtinguish
condensed aerosol generators shall not be located where they can be
mechanically damaged, exposed to chemicals, or to adverse weather conditions which may render
them inoperative. Suitable protective provisions shall be adopted, if necessary.
FirePro
Xtinguish
condensed aerosol generators shall be securely installed following the guidance
given by this manual.
9.1
Minimum Safe Distances
Minimum safe distances:
FirePro
Xtinguish
condensed aerosol generators shall not be installed at less than the minimum
safe distances as specified in the
FirePro
Xtinguish
condensed aerosol generator data sheets.
The generator datasheets are in Appendix C of this manual.
The minimum safe distance between the
FirePro
Xtinguish
condensed aerosol generator
casing and personnel shall be the distance from the generator casing to where the temperature
does not exceed 75°C (167°F) during and after discharge.
The minimum safe distance between the
FirePro
Xtinguish
condensed aerosol generator
casing and combustible materials shall be the distance from the generator casing to where the
temperature does not exceed 200°C (392°F) during and after discharge.
9.2
Safety Requirements
Personnel shall not enter a protected space during or after the agent discharge.
Safeguards shall be provided to ensure prompt evacuation of personnel prior to system discharge,
and to prevent entry or re-entry into the protected enclosure after system discharge.
There shall be provided a means for prompt rescue of any trapped personnel, including the following:
a. Provision for adequate egress pathways, and procedures to keep them clear at all times
b. Provision for emergency lighting and directional signs if necessary to ensure quick, safe
evacuation.
c. Provision for alarms in such areas that will operate immediately on detection of the fire.
d. Provision for only outward-swinging, self-closing doors at exits from hazardous areas and,
where such doors are latched, panic hardware shall be installed.
e. Provision for continuous alarms at entrances to such areas until the atmosphere has been
restored to normal.
f. Provision for warning and instruction signs at entrances to and inside such areas. These
signs should inform persons in or entering the protected area that an aerosol system is
installed and shall contain additional instructions pertinent to the conditions of the hazard.
g. Provision for the prompt discovery and rescue of persons rendered unconscious in such
areas. This should be accomplished by having such areas searched immediately by trained
personnel equipped with proper breathing equipment. Self-contained breathing equipment
and personnel trained in its use and in rescue practices, including cardiopulmonary
resuscitation, should be readily available.
h. Provision for instruction and drills for all personnel in or in the vicinity of such areas, including
maintenance or construction people, to ensure their correct action when a
FirePro
Xtinguish
condensed aerosol system operates.
Содержание FirePro Xtinguish
Страница 35: ...Page 35 of 113 FirePro Xtinguish I O Manual V1 05 UL...
Страница 36: ...Page 36 of 113 FirePro Xtinguish I O Manual V1 05 UL...
Страница 71: ...18 Appendix C FirePro Xtinguish Generator Datasheets...
Страница 72: ...Page 72 of 113 FirePro Xtinguish I O Manual V1 05 UL...
Страница 90: ...19 Appendix D FirePro Xtinguish Generator Drawings Xtinguish FNX 20S...
Страница 91: ...Page 91 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 20T...
Страница 92: ...Page 92 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 40S...
Страница 93: ...Page 93 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 80S...
Страница 94: ...Page 94 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 40T FNX 80T...
Страница 95: ...Page 95 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 40T FNX 80T...
Страница 96: ...Page 96 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 100S ELECTRICAL ACTUATOR...
Страница 97: ...Page 97 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 200S ELECTRICAL ACTUATOR...
Страница 98: ...Page 98 of 113 FirePro Xtinguish I O Manual V1 05 UL FNX 500S ELECTRICAL ACTUATOR...
Страница 99: ...Page 99 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 100S FNX 200S FNX 500S...
Страница 100: ...Page 100 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 1200 FNX 1200S...
Страница 101: ...Page 101 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 1200T FNX 1200TS...
Страница 102: ...Page 102 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 2000 FNX 2000S...
Страница 103: ...Page 103 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 2000T FNX 2000TS...
Страница 104: ...Page 104 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 3000 FNX 3000S...
Страница 105: ...Page 105 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 3000T FNX 3000TS...
Страница 106: ...Page 106 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 4200T FNX 4200TS...
Страница 107: ...Page 107 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 5700 FNX 5700S...
Страница 108: ...Page 108 of 113 FirePro Xtinguish I O Manual V1 05 UL Xtinguish FNX 5700T FNX 5700TS...