Appendix F: Technical Specification
64 (70)
F
Technical Specification
F.1
Functional Earth (FE) Requirements
In order to achieve proper EMC behavior, the product must be connected to functional earth (FE)
via the DIN-rail connector. If the DIN-rail cannot be used, FE must be connected to the power
connector.
HMS Networks AB does not guarantee proper EMC behavior unless these FE requirements are
fulfilled.
Make sure the DIN-rail is properly connected to FE.
F.2
Power Supply
Supply voltage
The HMS-EN2MB-R linking device requires a regulated 24
V (20.4 V to 28.8 V) DC power source.
Power consumption
The typical power consumption is 150 mA at 24 V.
F.3
Environmental Specification
Temperature
Operating
-25º to +70º Celsius
Non-operating
-40º to +85º Celsius
Relative humidity
The product is designed for a relative
humidity of 5% to 95% noncondensing.
Linking Device User Manual