Appendix E: CIP Objects
56 (70)
Class 3 Connection Details
General
Class 3 connections are used to establish connections towards the message router. Thereafter, the connection
is used for explicit messaging. Class 3 connections use TCP transport.
No. of simultaneous Class 3 connections:
16
Supported RPI (Requested Packet
Interval):
2... 10000 ms
T→O Connection type:
Point-to-point
O→-T Connection type:
Point-to-point
Supported trigger type:
Application
E.5
DLR Object (47h)
Category
Extended
Object Description
-
Supported Services
Class:
Get_Attribute_Single
Get_Attributes_All
Instance:
Get_Attribute_Single
Set_Attribute_Single
Class Attributes
#
Name
Access
Type
Value
1
Revision
Get
UINT
0002h (Object revision)
Instance Attributes
Attributes #1–4 and #6–7 an be customized by implementing the EtherNet/IP Host Object.
#
Name
Access
Type
Value/Description
1
Network
Topology
Get
USINT
Bit:
0
1
Contents:
“Linear”
“Ring”
2
Network Status Get
USINT
Bit:
0
1
2
3
4
Contents:
“Normal” (N/A)
“Ring Fault”
“Unexpected Loop Detected”
“Partial Network Fault”
“Rapid Fault/Restore Cycle”
Linking Device User Manual
scm-1202–181 2.0 en-US
Содержание Anybus HMS-EN2MB-R
Страница 1: ...Linking Device EtherNet IP to Modbus TCP USER MANUAL scm 1202 181 2 0 en US ENGLISH...
Страница 5: ...Linking Device User Manual scm 1202 181 2 0 en US H Copyright Notices 67...
Страница 6: ...This page intentionally left blank...
Страница 34: ...This page intentionally left blank...
Страница 64: ...Appendix E CIP Objects 62 70 Name Access Type Value Comments Linking Device User Manual scm 1202 181 2 0 en US...
Страница 71: ...This page intentionally left blank...