29 (70)
5
Verify Operation
5.1
Status LEDs
A test sequence is performed on all LEDs during startup.
At power up, LED 1 - 2 will indicate solid orange and LED 3 - 4 will indicate solid yellow for 15 - 30
seconds. This will be followed by a LED test sequence, performed on the (MS EN) Module Status and (NS)
Network Status LEDs.
An identification LED sequence can be performed on LEDs 1, 5 and 6 by clicking the “Wink device” button
in the linking device management section in the web configuration interface.
Name
Indication
Meaning
1 - Module Status
EtherNet/IP
Off
Alternating red/green
Flashing green
Green
Flashing red
Red
Power off
Boot sequence
Idle
Running
Major or minor recoverable
error
Major or minor unrecoverable
error (exception state or fatal)
2 - Network Status
EtherNet/IP
Off
Green
Flashing green
Red
Flashing red
Power off or no IP address
Online, one or more
connections established (CIP
class 1 or 3)
Online, no connections
established
Duplicate IP address, fatal error
One or more connections timed
out (CIP class 1 or 3)
3, 4 - Ethernet Link 1 & 2 Off
Flashing green
Flashing yellow
No link
Receiving/transmitting Ethernet
packets at 100 Mbit
Receiving/transmitting Ethernet
packets at 10 Mbit
5 - SD Card
Green
Red
Accessing SD card
Failure
6 - Modbus-TCP Status
Off
Green
Flashing green
Flashing red
Red
Power off
Communicating with Modbus-
TCP network
Idle
Transaction error or timeout
Fatal error
7, 8 - Modbus-TCP
Ethernet Link 1 & 2
Off
Flashing green
Flashing yellow
No link
Receiving/transmitting Ethernet
packets at 100 Mbit
Receiving/transmitting Ethernet
packets at 10 Mbit
Linking Device User Manual
scm-1202–181 2.0 en-US
Содержание Anybus HMS-EN2MB-R
Страница 1: ...Linking Device EtherNet IP to Modbus TCP USER MANUAL scm 1202 181 2 0 en US ENGLISH...
Страница 5: ...Linking Device User Manual scm 1202 181 2 0 en US H Copyright Notices 67...
Страница 6: ...This page intentionally left blank...
Страница 34: ...This page intentionally left blank...
Страница 64: ...Appendix E CIP Objects 62 70 Name Access Type Value Comments Linking Device User Manual scm 1202 181 2 0 en US...
Страница 71: ...This page intentionally left blank...