13 (70)
4
Configuration
4.1
Configuration Flow
The linking device can
only
be configured from within Studio 5000. This is done by configuring
the settings of a linking device imported into the current Studio 5000 project.
A separate Modbus-TCP client configuration manager is executed to handle the configuration. It
is included as an add-on profile and integrated in Studio 5000. The configuration manager is pre-
installed as part of your Studio 5000 installation. No separate installation is needed.
The linking device configuration is always automatically stored in the Studio 5000 project when
the Modbus-TCP client configuration manager is closed. The next time the configuration
manager is opened, the stored configuration is retrieved.
The linking device is configured in the following basic steps:
1.
In Studio 5000, set up and launch the HMS-EN2MB-R configuration manager (step 1–6 in
Studio 5000 Configuration Example, p. 15
).
2.
Configure the Modbus-TCP client. See step 7–13 in
Studio 5000 Configuration Example, p.
and
Modbus-TCP Client Configuration, p. 14
.
3.
Based on the client configuration, configure the tags that will be used in Studio 5000. The
configuration and status is automatically sent to Studio 5000 when the tag editor is closed.
See steps 14–16 in
Studio 5000 Configuration Example, p. 15
and
.
4.2
Configuration Requirements
The EtherNet/IP to Modbus-TCP linking device is configured over the EtherNet/IP port using the
pre-installed add-on profile in Studio 5000.
Three requirements must be met for the configuration manager to function:
•
The linking device must be powered on.
•
The linking device must be connected and available from the computer with the Studio
5000 installation.
•
Any switches or firewalls between the linking device and the computer with Studio
5000 must allow HTTP traffic.
This is only required to configure the device, not during operation.
4.3
Linking Device Configuration Manager
The foundation of theEtherNet/IP to Modbus-TCP linking device configuration manager is the tag
editor. It is the first view when you open the configuration manager. At first startup the editor
holds no tags.
Config Line
in the bottom bar shows if the EtherNet/IP connection between the PLC and the
Linking Device User Manual
scm-1202–181 2.0 en-US
Содержание Anybus HMS-EN2MB-R
Страница 1: ...Linking Device EtherNet IP to Modbus TCP USER MANUAL scm 1202 181 2 0 en US ENGLISH...
Страница 5: ...Linking Device User Manual scm 1202 181 2 0 en US H Copyright Notices 67...
Страница 6: ...This page intentionally left blank...
Страница 34: ...This page intentionally left blank...
Страница 64: ...Appendix E CIP Objects 62 70 Name Access Type Value Comments Linking Device User Manual scm 1202 181 2 0 en US...
Страница 71: ...This page intentionally left blank...