Appendix E: CIP Objects
61 (70)
#
Name
Access
Type
Value
Comments
1:
Enable ACD (Default).
If ACD (address conflict
detection) is enabled, bit 6 in
attribute #1 will be set if an
ACD conflict is detected. The
Network Status LED will also
indicate a detected conflict.
11
LastConflictDe-
tected
Set
Struct of:
ACD Diagnostic parameters Related to the
last conflict detected.
AcdActiviity
USINT
-
State of ACD activity when last
conflict detected.
RemoteMAC
ARRAY of 6 USINT -
MAC address of remote node
form the ARP PDU in which a
conflict was detected.
ArpPdu
ARRAY of 28
USINT
-
Copy of the raw ARP PDU in
which a conflict was detected.
E.10
Ethernet Link Object (F6h)
Category
Extended
Object Description
This object maintains link specific counters and status information for an IEEE 802.3 communications interface.
Exactly one instance for each communications interface on the module is supported. Instances for internally
accessible interfaces can also be supported.
Supported Services
Class:
Get_Attributes_All
Get_Attribute_Single
Instance:
Get_Attributes_All
Get_Attribute_Single
Set_Attribute_Single
Get_And_Clear
Class Attributes
#
Name
Access
Type
Value
1
Revision
Get
UINT
0003h (Object revision)
2
Max Instance
Get
UINT
3 (Maximum instance number)
3
Number of
Instances
Get
UINT
3 (Number of instances)
Instance Attributes
#
Name
Access
Type
Value
Comments
1
Interface
Speed
Get
UDINT
10 or 100
Actual Ethernet interface speed.
2
Interface Flags
Get
DWORD
-
See table “Interface Flags” below.
3
Physical
Address
Get
Array of 6 USINTs
(MAC ID)
Physical network address, i.e. assigned
MAC address.
Linking Device User Manual
scm-1202–181 2.0 en-US
Содержание Anybus HMS-EN2MB-R
Страница 1: ...Linking Device EtherNet IP to Modbus TCP USER MANUAL scm 1202 181 2 0 en US ENGLISH...
Страница 5: ...Linking Device User Manual scm 1202 181 2 0 en US H Copyright Notices 67...
Страница 6: ...This page intentionally left blank...
Страница 34: ...This page intentionally left blank...
Страница 64: ...Appendix E CIP Objects 62 70 Name Access Type Value Comments Linking Device User Manual scm 1202 181 2 0 en US...
Страница 71: ...This page intentionally left blank...