SJ200
2
Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–55
The Error for the PID loop is the magni-
tude (absolute value) of the difference
between the Setpoint (desired value) and
Process Variable (actual value). The PID
output deviation signal [OD] (output
terminal function option code 04)
indicates when the error magnitude has
exceeded a magnitude you define.
PID Error (PV–SP) deviation threshold
Deviation
signal
t
t
SP
Output
PV
0
1
0
C044
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
C041 Overload level setting
Sets the overload signal level
between 0% and 200% (from 0
to two times the rated current
of the inverter)
✘ ✔
Rated current
for each inverter
model
A
OL LVL 001.60A
C241 Overload level setting,
2nd motor
Sets the overload signal level
between 0% and 200% (from 0
to two times the rated current
of the inverter)
✘ ✔
Rated current
for each inverter
model
A
2OLLVL 001.60A
C042 Frequency arrival
setting for acceleration
Sets the frequency arrival
setting threshold for the output
frequency during acceleration,
range is 0.0 to 400.0 Hz
✘ ✔
0.0
0.0
Hz
ARV ACC 0000.0Hz
C043 Arrival frequency
setting for deceleration
Sets the frequency arrival
setting threshold for the output
frequency during deceleration,
range is 0.0 to 400.0 Hz
✘ ✔
0.0
0.0
Hz
ARV DEC 0000.0Hz
C044 PID deviation level
setting
Sets the allowable PID loop
error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%
✘ ✔
3.0
3.0
%
ARV PID 003.0%
C052 PID FBV function
high limit
When the PV exceeds this
value, the PID loop turns OFF
the PID Second Stage Output,
range is 0.0 to 100.0%
✘ ✔
100.0
100.0
%
PID LtU 0100.0%
C053 PID FBV function
variable low limit
When the PV goes below this
value, the PID loop turns ON
the PID Second Stage Output,
range is 0.0 to 100.0%
✘ ✔
0.0
0.0
%
PID LtL 0000.0%
Содержание SJ2002 Series
Страница 2: ......
Страница 46: ......
Страница 203: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 214: ......
Страница 231: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 282: ......
Страница 283: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 295: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 299: ...SJ2002 Inverter Appendix D D 5 L1 L2 L3 PE SJ2002 inverter with book type filter M 3 ...