ModBus Data Listing
Appendix B
B–26
The following table lists the holding registers for the “A” Group Standard Functions.
Holding Registers for “A” Group Standard Functions
Func.
Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
A001
Frequency source
setting
R/W Five options; select codes:
00 .. Keypad potentiometer
01 .. Control terminal
02 .. Function F001 setting
03 .. ModBus network input
10 .. Calculate function output
1019h
04121
0 to 3, 10
—
A002
Run command source
setting
R/W Three options; select codes:
01 .. Control terminal
02 .. Run key on keypad, or
digital operator
03 .. ModBus network input
101Ah 04122
1, 2, 3
—
A003
Base frequency setting
R/W Settable from 30 Hz to the
maximum frequency
101Bh 04123
30 to
max. freq.
1 Hz
A203
Base frequency setting,
2nd motor
R/W Settable from 30 Hz to the
2nd maximum frequency
150Ch 05388
30 to
max. freq.
2
1 Hz
A004
Maximum frequency
setting
R/W Settable from the base
frequency up to 400 Hz
101Ch 04124
30 to 400
1 Hz
A204
Maximum frequency
setting, 2nd motor
R/W Settable from the 2nd base
frequency up to 400 Hz
150Dh 05389
30 to 400
1 Hz
A005
[AT] selection
R/W Four options, select codes:
00 .. Select between [O] and
[OI] at [AT]
01 .. [O] + [OI] ([AT] input is
ignored)
02 .. Select between [O] and
keypad potentiometer
03 .. Select between [OI] and
keypad potentiometer
101Dh 04125
0, 1, 2, 3
—
A011
O–L input active range
start frequency
R/W The output frequency corre-
sponding to the analog input
range starting point,
range is 0.0 to 400.0
1020h
04128
0 to 4000
0.1 Hz
A012
O–L input active range
end frequency
R/W The output frequency corre-
sponding to the analog input
range ending point,
range is 0.0 to 400.0
1022h
04130
0 to 4000
0.1 Hz
A013
O–L input active range
start voltage
R/W The starting point (offset) for
the active analog input range,
range is 0. to 100
1023h
04131
0 to 100
1 %
Содержание SJ2002 Series
Страница 2: ......
Страница 46: ......
Страница 203: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 214: ......
Страница 231: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 282: ......
Страница 283: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 295: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 299: ...SJ2002 Inverter Appendix D D 5 L1 L2 L3 PE SJ2002 inverter with book type filter M 3 ...