PID Loop Operation
Oper
ations
and Monitor
ing
4–58
PID Loop Configuration
The inverter’s PID loop algorithm is configurable for various applications.
PID Output Limit -
The PID loop controller has a built-in output limit function. This
function monitors the difference between the PID setpoint and the loop output (inverter
output frequency), measured as a percentage of the full scale range of each. The limit is
specified by parameter A078.
• When the difference |(Setpoint – loop output)| is smaller than or equal to the A078
limit value, the loop controller operates in its normal linear range.
• When the difference |(Setpoint – loop output)| is larger than the A078 limit value, the
loop controller changes the output frequency as needed so that the difference does not
exceed the limit.
The diagram below shows PID setpoint changes and the related output frequency
behavior when a limit value in A078 exists.
Error Inversion -
In typical heating loops or ventilation loops, an increase in energy
into the process results in an
increasing
PV. In this case, the Loop Error = (SP – PV). For
cooling loops, an increase in energy into the process results in a
decreasing
PV. In this
case, the Loop Error = –(SP – PV). Use A077 to configure the error term.
Other PID-related topics:
•
“PID Control” on page 3–23
•
“PID ON/OFF and PID Clear” on page 4–29
•
“Output Deviation for PID Control” on page 4–43
•
“PID Second Stage Output” on page 4–47
Limit value
PID Setpoint
t
A078
Limit value
A078
Output limit
Output limit
%
Limit imposed
on output
Limit imposed
on output
Output frequency
∑
PID
Calculation
SP
Error
Freq.
PV from process with
positive
correlation
PV
+
–
A077 = 00
∑
PID
Calculation
SP
Error
Freq.
PV from process with
negative
correlation
PV
–
+
A077 = 01
Содержание SJ2002 Series
Страница 2: ......
Страница 46: ......
Страница 203: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 214: ......
Страница 231: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 282: ......
Страница 283: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 295: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 299: ...SJ2002 Inverter Appendix D D 5 L1 L2 L3 PE SJ2002 inverter with book type filter M 3 ...