“C” Group: Intelligent Terminal Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–54
Analog Function Summary Table –
This table shows both functions for the analog
voltage output [AM] terminal, configured by C028. More information on using and
calibrating the [AM] output terminal is in
“Analog Output Operation” on page 4–56
.
Output Function Adjustment Parameters
The following parameters work in
conjunction with the intelligent output
function, when configured. The overload
level parameter (C041) sets the motor
current level at which the overload signal
[OL] turns ON. The range of settings is
from 0% to 200% of the rated current for
the inverter. This function is for generating
an early warning logic output, without
causing either a trip event or a restriction
of the motor current (those effects are available on other functions).
The frequency arrival signal, [FA1] or
[FA2], is intended to indicate when the
inverter output has reached (arrived at) the
target frequency. You can adjust the timing
of the leading and trailing edges of the
signal via two parameters specific to accel-
eration and deceleration ramps, C042 and
C043.
09
LOG
Logic Output
Function
ON
when the Boolean operation specified by C143
has a logical “1” result
OFF
when the Boolean operation specified by C143
has a logical “0” result
10
ODc
Option Card
Detection Signal
ON
when the communications watchdog timer
(period specified by P044) has timed out
OFF
when the communications watchdog timer is
satisfied by regular communications activity
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
Analog Function Summary Table
Option
Code
Function Name
Description
Range
00
Analog Frequency
Monitor
Actual motor speed
0 to max.
frequency in Hz
01
Analog Current Output
Monitor
Motor current (% of maximum rated
output current)
0 to 200%
Motor current
Overload
signal
t
t
0
1
0
C041
Output
frequency
Arrival
signal
t
t
0
1
0
C042
C043
Содержание SJ2002 Series
Страница 2: ......
Страница 46: ......
Страница 203: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 214: ......
Страница 231: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 282: ......
Страница 283: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 295: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 299: ...SJ2002 Inverter Appendix D D 5 L1 L2 L3 PE SJ2002 inverter with book type filter M 3 ...