Using the Front Panel Keypad
In
v
e
rter Mounting
and Installation
2–26
Keys, Modes, and Parameters
The purpose of the keypad is to provide a way to change
modes and parameters. The term
function
applies to both
monitoring modes and parameters. These are all accessible
through
function codes
that are primarily 4-character
codes. The various functions are separated into related
groups identifiable by the left-most character, as the table
shows.
For example, function “A004” is the
base frequency setting
for the motor, typically
50 Hz or 60 Hz. To edit the parameter, the inverter must be in Program Mode (PRG LED
will be ON). You use the front panel keys to first select the function code “A004.” After
displaying the value for “A004,” use the Up/Down (
or
) keys to edit it.
NOTE:
The inverter 7-segment display shows lower case “b” and “d,” meaning the same
as the upper case letters “B” and “D” used in this manual (for uniformity “A to F”).
The inverter automatically switches into Monitor
Mode when you access “D” Group functions. It
switches into Program Mode when you access
any other group, because they all have editable
parameters. Error codes use the “E” Group, and
appear automatically when a fault event occurs.
Refer to
“Monitoring Trip Events, History, &
Conditions” on page 6–5
for error code details.
Function
Group
Type (Category) of Function
Mode to Access
PRG LED
Indicator
“D”
Monitoring functions
Monitor
“F”
Main profile parameters
Program
“A”
Standard functions
Program
“B”
Fine tuning functions
Program
“C”
Intelligent terminal functions
Program
“H”
Motor constant functions
Program
“E”
Error codes
—
—
1
2
d
0 0 1
POWER
ALARM
Hz
A
RUN
PRG
RUN
STOP
RESET
FUNC.
STR
HITACHI
1
2
1
2
A - - -
POWER
ALARM
Hz
A
RUN
PRG
RUN
STOP
RESET
FUNC.
STR
HITACHI
1
2
A 0 0 4
POWER
ALARM
Hz
A
RUN
PRG
RUN
STOP
RESET
FUNC.
STR
HITACHI
1
2
5 0.0
POWER
ALARM
Hz
A
RUN
PRG
RUN
STOP
RESET
FUNC.
STR
HITACHI
FUNC.
FUNC.
“D” Group
MONITOR
PROGRAM
“A” Group
“B” Group
“C” Group
“F” Group
“H” Group
“D” Group
Содержание SJ2002 Series
Страница 2: ......
Страница 46: ......
Страница 203: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 214: ......
Страница 231: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 282: ......
Страница 283: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 295: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 299: ...SJ2002 Inverter Appendix D D 5 L1 L2 L3 PE SJ2002 inverter with book type filter M 3 ...