APPENDIX PARAMETER OBJECT LISTS
41
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
Display Select (Param167)
1
137
1
00(All Display)/
01(Each Func Display)/
02(User setting)/
03(Data comparison
display)/04(basic display)
1
Get/Set
b037
Initial-screen selection
(Param417)
1
138
1
00(Screen displayed when the STR
key was pressed last)/
01(d001)/02(d002) / 03(d003) /
04(d007) / 05(F001)
1
Get/Set
b038
Automatic user-parameter
setting function enable
(Param418)
1
139
1
00(Invalid)/01(Valid)
1
Get/Set
b039
TorqueLimit Mode (Param168)
1
140
1
00(4 Quadrant mode)/
01(Terminal)/02(Analog input)/
03(Option1)/04(Option2)
1
Get/Set
b040
TorqueLimit Lvl1 (Param169)
1
141
1
0 to 200(%),255 (~55KW)
0 to 180(%),255 (75~132KW)
1
Get/Set
b041
TorqueLimit Lvl2 (Param170)
1
142
1
0 to 200(%),255 (~55KW)
0 to 180(%),255 (75~132KW)
1
Get/Set
b042
TorqueLimit Lvl3 (Param171)
1
143
1
0 to 200(%),255 (~55KW)
0 to 180(%),255 (75~132KW)
1
Get/Set
b043
TorqueLimit Lvl4 (Param172)
1
144
1
0 to 200(%),255 (~55KW)
0 to 180(%),255 (75~132KW)
1
Get/Set
b044
Torq LADSTOP Sel (Param173)
1
145
1
00(Invalid)/01(Valid)
1
Get/Set
b045
RV-RunPreventSel (Param174)
1
146
1
00(Invalid)/01(Valid)
1
Get/Set
b046
IPNonStopModeSel (Param175)
1
150
1
00(Invalid)/01(Valid)/
02(DC Voltage Constant Control,
With Resume)/
03(Without Resume)
1
Get/Set
b050
IPNonStopStart-V (Param176)
1
151
2
0.0 to 999.9(V)
10
Get/Set
b051
IP OV-LADSTOPLvl (Param177)
1
152
2
0.0 to 999.9(V)
10
Get/Set
b052
IPNonStopDecTime (Param178)
1
153
4
0.01 to 3600.00(s)
100
Get/Set
b053
IP StartDec-Freq (Param179)
1
154
2
0.00 to 10.00(Hz)
100
Get/Set
b054
Max-limit level of O (Param419)
1
160
1
0. to 100. (%)
(lower limit : b061 + b062 * 2) (%)
1
Get/Set
b060
Min-limit level of O (Param420)
1
161
1
0. to 100. (%)
(upper limit : b060 - b062 * 2) (%)
1
Get/Set
b061
Hysteresis width of O
(Param421)
1
162
1
0. to 100. (%)
(upper limit : b061 - b062 / 2) (%)
1
Get/Set
b062
Max-limit level of OI (Param422)
1
163
1
0. to 100. (%)
(lower limit : b064 + b066 * 2) (%)
1
Get/Set
b063
Min-limit level of OI (Param423)
1
164
1
0. to 100. (%)
(upper limit : b063 - b066 /*2) (%)
1
Get/Set
b064
Hysteresis width of OI
(Param424)
1
165
1
0. to 100. (%)
(upper limit : b063 - b064 / 2) (%)
1
Get/Set
b065
Max-limit level of O2
(Param425)
1
166
1
0. to 100. (%)
(lower limit : b067 + b068 * 2) (%)
1
Get/Set
b066
Min-limit level of O2 (Param426)
1
167
1
0. to 100. (%)
(upper limit : b066 - b068 * 2) (%)
1
Get/Set
b067
Hysteresis width of O2
(Param427)
1
168
1
0. to 100. (%)
(upper limit : b066 - b067 / 2) (%)
1
Get/Set
b068
Operation level at O
disconnection (Param428)
1
170
1
0 to 100(%)/no
1
Get/Set
b070
Operation level at OI
disconnection (Param429)
1
171
1
0 to 100(%)/no
1
Get/Set
b071
Operation level at O2
disconnection (Param430)
1
172
1
-100 to 100(%)/no
1
Get/Set
b072
Cumulative input power data
clearance (Param431)
1
178
1
00(OFF)/01(ON)
1
Get/Set
b078
Cumulative input power display
gain setting (Param432)
1
179
2
1 to 1000
1
Get/Set
b079
Start Frequency (Param57)
1
182
2
0.1 to 9.99(Hz)
100
Get/Set
b082