CHAPTER 4 SETTING
7
4.1 Setting methods of Baud rate and MAC ID
Follow the procedure as below to set Baud rate in DeviceNet and MAC ID, reset the power supply after
changing the setting (setting will be reflected after resetting power supply.). Initialization Baud rate: 125kbps,
Initialization MAC ID: 0.
4.1.1 Setting method of Baud rate
The table below is the setting method of Baud rate (Front view of the option board.).
( , indicate direction for switch of Dip switch)
Baud rate
125kbps
250kbps
500kbps
Dip switch
Setting
(Note) Do not switch on DR1 and DR0 at the same time.
4.1.2 Setting method of MAC ID
The table as below is the setting method of MAC ID (Front view of the option board).
MAC ID
Dip switch setting
Figure left describes the direction of Dip switches. See below.
Bottom: 0 Upper: 1
Bit increases from right to left switches.
Therefore, figure left becomes formula as below.
1 2
5
+0 2
4
+1 2
3
+0 2
2
+0 2
1
+1 2 =29(Hex)=41(dec)
4.2 Setting of the Inverter
The following table describes setting items which relates SJ700/SJ300/L300P series Inverters with SJ-DN2.
To set appropriate settings, refer to inverter instruction manual “chapter 3 Operation”, “chapter 4
Explanation of function” and this manual.
Code
Function
Range of data
Initial
data
Setting on
run
Change
mode on
run
Setting
P044
DeviceNet
communication
watchdog timer
0.00 to 99.99(sec)
setting resolution 10nsec
Case of set to 0.00, this func. Is disable.
1.00
impossible
impossible
P045
Inverter action on
communication error
00(trip)/01(trip after deceleration stop)/
02(ignore)/03(free run)/
04(deceleration stop)
01
impossible
impossible
P046
Polled I/O OUTPUT
Instance number
20, 21, 100
21
impossible
impossible
P047
Polled I/O INPUT
Instance number
70, 71, 101
71
impossible
impossible
P048
Inverter action on
Idle mode
00(trip)/01(trip after deceleration stop)/
02(ignore)/03(free run)/
04(deceleration stop)
01
impossible
impossible
P049
Motor poles setting
for revolutions per
minute
0 to 38
Only even number is possible to set.
set to 0:setting and monitoring by [Hz]
except for 0:setting and monitoring by
[min
-1
]
0
impossible
impossible
Set data
when it
is need.
NA32
NA16
NA8
NA4
NA2
NA1
ON
OFF
DR1 DRO
DR
ON
OFF
DR1 DRO
DR
ON
OFF
DR1 DRO
DR
NA32 NA16 NA8 NA4 NA2 NA1
1
0
MAC ID