APPENDIX PARAMETER OBJECT LISTS
28
(3) Extend Group B object Class ID=103
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
Restart Mode Sel (Param143)
1
101
1
00(Trip)/01(0Hz Start)/
02(Synchronize)/
03(Sync& Stop& Trip)
1
Get/Set
b001
Allowable UVTime (Param144)
1
102
1
0.3 to 1.0(s)
10
Get/Set
b002
Restart WaitTime (Param145)
1
103
2
0.3 to 100.0(s)
10
Get/Set
b003
IP/UVTrip AtStop (Param146)
1
104
1
00(Invalid)/01(Valid)/
02(Invalid on stop)
1
Get/Set
b004
IP/UVRestartTime(Param147)
1
105
1
00(16 times)/01(Free)
1
Get/Set
b005
Open-phaseSelect (Param148)
1
106
1
00(Invalid)/01(Valid)
1
Get/Set
b006
FreqSet To Match (Param149)
1
107
4
0.00 to 400.00(Hz)
100
Get/Set
b007
E-Thermal Level (Param150)
1
112
2
20 to 120(%)(constant current)
1
Get/Set
b012
2nd E-ThermalLvl (Param349)
2
112
2
20 to 120(%)(constant current)
1
Get/Set
b212
3rd E-ThermalLvl (Param380)
3
112
2
20 to 120(%)(constant current)
1
Get/Set
b312
E-ThermalCharSel (Param151)
1
113
1
00(Reduced torque)/
01(Constant torque)/
02(Free setting)
1
Get/Set
b013
2ndEThermCharSel (Param350)
2
113
1
00(Reduced torque)/
01(Constant torque)/
02(Free setting)
1
Get/Set
b213
3rdEThermCharSel (Param381)
3
113
1
00(Reduced torque)/
01(Constant torque)/
02(Free setting)
1
Get/Set
b313
E-Thermal Freq 1 (Param152)
1
115
2
0 to 400(Hz)
1
Get/Set
b015
E-Thermal Cur 1 (Param153)
1
116
2
0.0 to 999.9(A)
10
Get/Set
b016
E-Thermal Freq 2 (Param154)
1
117
2
0 to 400(Hz)
1
Get/Set
b017
E-Thermal Cur 2 (Param155)
1
118
2
0.0 to 999.9(A)
10
Get/Set
b018
E-Thermal Freq 3 (Param156)
1
119
2
0 to 400(Hz)
1
Get/Set
b019
E-Thermal Cur 3 (Param157)
1
120
2
0.0 to 999.9(A)
10
Get/Set
b020
OL Limit Enable (Param158)
1
121
1
00(Inactive)/01(Inactive at dec 1)/
02(Active at const 1)/
03(Inactive at dec 2)
1
Get/Set
b021
OL Limit Level (Param159)
1
122
2
50 to 200(%) (~55KW)
50 to 180(%) (75~132KW)
1
Get/Set
b022
OL Limit Const (Param160)
1
123
2
0.1 to 30.00
100
Get/Set
b023
OL Limit Enable2 (Param161)
1
124
1
00(Inactive)/01(Inactive at dec 1)/
02(Active at const 1)/
03(Inactive at dec 2)
1
Get/Set
b024
OL Limit Level 2 (Param162)
1
125
2
50 to 200(%) (~55KW)
50 to 180(%) (75~132KW)
1
Get/Set
b025
OL Limit Const 2 (Param163)
1
126
2
0.1 to 30.00
100
Get/Set
b026
SoftLock ModeSel (Param383)
1
131
1
00(SFT - All param)/
01(SFT - Only freq)/
02(All param)/03(Only freq)/
10(Change mode on run)
1
Get/Set
b031
Run/P-ONTime Lvl (Param164)
1
134
2
0 to 65535(hr)
1
Get/Set
b034
FW/RV Restrict (Param165)
1
135
1
00(FW/RV Enable)/
01(Forward only)/02(Reverse only)
1
Get/Set
b035
ReducedV TimeSel (Param166)
1
136
1
00 to 06
1
Get/Set
b036
Display Select (Param167)
1
137
1
00(All Display)/
01(Each Func Display)/
02(User setting)
1
Get/Set
b037
TorqueLimit Mode (Param168)
1
140
1
00(4 Quadrant mode)/
01(Terminal)/02(Analog input)/
03(Option1)/04(Option2)
1
Get/Set
b040
TorqueLimit Lvl1 (Param169)
1
141
1
0 to 200(%)/255 (~55KW)
0 to 180(%)/255 (75~132KW)
1
Get/Set
b041
TorqueLimit Lvl2 (Param170)
1
142
1
0 to 200(%)/255 (~55KW)
0 to 180(%)/255 (75~132KW)
1
Get/Set
b042
TorqueLimit Lvl3 (Param171)
1
143
1
0 to 200(%)/255 (~55KW)
0 to 180(%)/255 (75~132KW)
1
Get/Set
b043
TorqueLimit Lvl4 (Param172)
1
144
1
0 to 200(%)/255 (~55KW)
0 to 180(%)/255 (75~132KW)
1
Get/Set
b044
Torq LADSTOP Sel (Param173)
1
145
1
00(Invalid)/01(Valid)
1
Get/Set
b045
RV-RunPreventSel (Param174)
1
146
1
00(Invalid)/01(Valid)
1
Get/Set
b046
IPNonStopModeSel (Param175)
1
150
1
00(Invalid)/01(Valid)
1
Get/Set
b050
IPNonStopStart-V (Param176)
1
151
2
0.0 to 999.9(V)
10
Get/Set
b051
IP OV-LADSTOPLvl (Param177)
1
152
2
0.0 to 999.9(V)
10
Get/Set
b052
IPNonStopDecTime (Param178)
1
153
4
0.01 to 3600.00(s)
100
Get/Set
b053
IP StartDec-Freq (Param179)
1
154
2
0.00 to 10.00(Hz)
100
Get/Set
b054
AM Adjustment (Param180)
1
180
1
0 to 255
1
Get/Set
b080