APPENDIX PARAMETER OBJECT LISTS
26
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com-
mand
O2 Function Sel (Param67)
1
106
1
00(Invalid)/01(O/OI-no reverse)/
02(O/OI-reverse)
1
Get/Set
A006
O Start Freq Set (Param68)
1
111
4
0.00 to 400.00(Hz)
100
Get/Set
A011
O End Freq Set (Param69)
1
112
4
0.00 to 400.00(Hz)
100
Get/Set
A012
O Start Rate (Param70)
1
113
1
0 to 100(%)
1
Get/Set
A013
O End Rate (Param71)
1
114
1
0 to 100(%)
1
Get/Set
A014
O Start Mode Sel (Param72)
1
115
1
00(Set frequency)/01(0Hz)
1
Get/Set
A015
Analog Sampling (Param73)
1
116
1
1 to 30
1
Get/Set
A016
Multi-Speed Mode (Param74)
1
119
1
00(Binary)/01(Bit)
1
Get/Set
A019
Multi-Speed 0 (Param75)
1
120
4
0.00 to 400.00(Hz)
100
Get/Set
A020
2nd Multi-Speed0 (Param339)
2
120
4
0.00 to 400.00(Hz)
100
Get/Set
A220
3rd Multi-Speed0 (Param374)
3
120
4
0.00 to 400.00(Hz)
100
Get/Set
A320
Multi-Speed 1 (Param76)
1
121
4
0.00 to 400.00(Hz)
100
Get/Set
A021
Multi-Speed 2 (Param77)
1
122
4
0.00 to 400.00(Hz)
100
Get/Set
A022
Multi-Speed 3 (Param78)
1
123
4
0.00 to 400.00(Hz)
100
Get/Set
A023
Multi-Speed 4 (Param79)
1
124
4
0.00 to 400.00(Hz)
100
Get/Set
A024
Multi-Speed 5 (Param80)
1
125
4
0.00 to 400.00(Hz)
100
Get/Set
A025
Multi-Speed 6 (Param81)
1
126
4
0.00 to 400.00(Hz)
100
Get/Set
A026
Multi-Speed 7 (Param82)
1
127
4
0.00 to 400.00(Hz)
100
Get/Set
A027
Multi-Speed 8 (Param83)
1
128
4
0.00 to 400.00(Hz)
100
Get/Set
A028
Multi-Speed 9 (Param84)
1
129
4
0.00 to 400.00(Hz)
100
Get/Set
A029
Multi-Speed 10 (Param85)
1
130
4
0.00 to 400.00(Hz)
100
Get/Set
A030
Multi-Speed 11 (Param86)
1
131
4
0.00 to 400.00(Hz)
100
Get/Set
A031
Multi-Speed 12 (Param87)
1
132
4
0.00 to 400.00(Hz)
100
Get/Set
A032
Multi-Speed 13 (Param88)
1
133
4
0.00 to 400.00(Hz)
100
Get/Set
A033
Multi-Speed 14 (Param89)
1
134
4
0.00 to 400.00(Hz)
100
Get/Set
A034
Multi-Speed 15 (Param90)
1
135
4
0.00 to 400.00(Hz)
100
Get/Set
A035
JoggingFrequency (Param91)
1
138
2
0.00 to 9.99(Hz)
100
Get/Set
A038
Jog StopMode Sel (Param92)
1
139
1
00(Free run)/01(Deceleration)/
02(DC Braking)/03(R-Free run)/
04(R-Deceleration)/
05(R-DC Braking)
1
Get/Set
A039
Torque Boost Sel (Param93)
1
141
1
00(Manual)/01(Automatic)
1
Get/Set
A041
2ndTrq-Boost Sel (Param340)
2
141
1
00(Manual)/01(Automatic)
1
Get/Set
A241
TorqueBoostValue (Param94)
1
142
1
0.0 to 20.0(%)
10
Get/Set
A042
2ndTrqBoostValue (Param341)
2
142
1
0.0 to 20.0(%)
10
Get/Set
A242
3rdTrqBoostValue (Param375)
3
142
1
0.0 to 20.0(%)
10
Get/Set
A342
TorqueBoostPoint (Param95)
1
143
2
0.0 to 50.0(%)
10
Get/Set
A043
2ndTrqBoostPoint (Param342)
2
143
2
0.0 to 50.0(%)
10
Get/Set
A243
3rdTrqBoostPoint (Param376)
3
143
2
0.0 to 50.0(%)
10
Get/Set
A343
Control Select (Param96)
1
144
1
00(Constant torque)/
01(Reduced torque)/
02(Free setting V/f)/
03(SLV control)/
04(0Hz-SLV control)/
05(Sensoring vector control)
1
Get/Set
A044
2ndControlSelect (Param343)
2
144
1
00(Constant torque)/
01(Reduced torque)/
02(Free setting V/f)/
03(SLV control)/
04(0Hz-SLV control)
1
Get/Set
A244
3rdControlSelect (Param377)
3
144
1
00(Constant torque)/
01(Reduced torque)/
02(Free setting V/f)
1
Get/Set
A344
Out-Voltage Gain (Param97)
1
145
1
20 to 100
1
Get/Set
A045
DC Brake Enable (Param98)
1
151
1
00(invalid)/01(Valid)
1
Get/Set
A051
DC Br Start Freq (Param99)
1
152
2
0.00 to 60.00(Hz)
100
Get/Set
A052
DC Br Wait Time (Param100)
1
153
1
0.0 to 5.0(s)
10
Get/Set
A053
DC Brake Power (Param101)
1
154
1
0 to 100(%) (~55KW)
0 to 80(%) (75~132KW)
1
Get/Set
A054
DC Brake Time (Param102)
1
155
2
0.0 to 60.0(s)
10
Get/Set
A055
DC Brake ModeSel (Param103)
1
156
1
00(Edge)/01(Level)
1
Get/Set
A056
DCBrPowerAtStart (Param104)
1
157
1
0 to 100(%) (~55KW)
0 to 80(%) (75~132KW)
1
Get/Set
A057
DCBrTime AtStart (Param105)
1
158
2
0.0 to 60.0(s)
10
Get/Set
A058
DCBr CarrierFreq (Param106)
1
159
1
0.5 to 15.0(kHz) (~55KW)
0.5 to 10.0(kHz) (75~132KW)
10
Get/Set
A059
Upper Freq Limit (Param59)
1
161
4
0.00 to 400.00(Hz)
100
Get/Set
A061
2ndUpperFRQLimit (Param336)
2
161
4
0.00 to 400.00(Hz)
100
Get/Set
A261
Lower Freq Limit (Param58)
1
162
4
0.00 to 400.00(Hz)
100
Get/Set
A062
2ndLowerFRQLimit (Param335)
2
162
4
0.00 to 400.00(Hz)
100
Get/Set
A262