8 EXPLANATION OF OPERATION
- 92 -
8.9 Output Timing of the PCs OK Signal
When the ladder program execution switch on the CPU module is switched from STOP to
RUN, output of the PCs OK signal changes as shown below.
RUN (NORM)
STOP
OFF
ON
Ladder program
execution switch
PCs OK
signal
Ladder diagram
program
90 to 120 ms
(equivalent to four sequence cycles)
Stopping
Operating
Specifications of the PCs OK signal
Output type: Relay output (insulation by a relay)
Rated outputs: 100 VAC; 12 to 24 VDC, 2A; 48 VDC, 0.5 A; 100 VAC, 0.1 A
Minimum output: 10 VDC, 20 mA
Response time: 15 ms or less
Cable: Twisted-pair cable, 100 m or less