Setting the DIP switches
SMGB0066 rev.0 - 12/2009
Electrical wiring
Service Manual
3
3.2.2. Main switches and fuses
Select the main switches (current breaker) according to the next table:
Model
Power source
CB
(Circuit Break) (A)
ElB
(Earth leakage Breaker)
(number of poles/A/mA)
RHUE-3AVHN
1~ 230V 50Hz
32
2/40/30
RHUE-4AVHN
32
RHUE-5AVHN
32
RHUE-6AVHN
32
RHUE-5AHN
3N~ 400V 50Hz
20
4/40/30
RHUE-6AHN
20
3.3. SETTInG THE dIP SWITCHES
• number and position of dIP switches
The PCB of the Yutaki unit contains 9 DIP switches.
DIP switches location on the PCB:
Upper side shows unit status
Lower side shows discharge
and suction pressure value
alternatively
Status indication
1.
Press the PSW2 more than 3 seconds to
change the status display mode
Alarm history
2.
Press the PSW1 and PSW2 together more
than 3 seconds to switch to alarm history
mode
note
The mark “
-
■
“ indicates the position of dips switches.
No mark “
-
■
” or "not available" indicates pin position is not affecting.
The figures show the settings before shipment or after selection.
-
"Not used" means that the pin must not be changed. A malfunction might happen if changed.
-
note
Before setting dips switches, first turn the power source off. Otherwise, the changes will not be taken into
-
account.
Содержание RHUE-3AVHN
Страница 1: ...Air to water Heat pump RHUE 3AVHN RHUE 4AVHN RHUE 5A V HN RHUE 6A V HN YUTAKI SERIES RHUE A V HN ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 16: ......
Страница 34: ......
Страница 70: ......
Страница 166: ......
Страница 236: ...Spare parts Service Manual 234 Spare parts of Yutaki SMGB0066 rev 0 12 2009 8 2 2 DHWT Domestic Hot Water Tank ...
Страница 238: ......
Страница 260: ......
Страница 261: ......
Страница 262: ...SMGB0066 rev 0 12 2009 Printed in Spain ...