Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
7.2. TroUBlESHooTInG ProCEdUrE
● Checking using the 7-segment display.
7-seg. display info.
Upper side
Lower side
(See the following table for details)
General Indication
Content
88
Proceeding Initialization
88
Power ON (During unit stoppage)
U
Pump Operation (During unit stoppage)
U
Waiting of pump feedback (During unit operation)
Stoppage by Thermo-OFF
Heating operation (Normal operation)
↔
Heating operation (Activation of forced compressor frequency control due to low
pressure difference:forced up)
↔
Heating operation (Activation of forced compressor frequency control due to high
pressure difference:forced down)
↔
Heating operation (Activation of forced compressor frequency control due to
excessively high discharge pressure: forced down)
↔
Heating operation (Activation of forced compressor frequency control due to
excessively high current :forced down)
↔
Heating operation (Activation of forced compressor frequency control due to
excessively high inverter fin temperature: forced down)
↔
Retry operation (by alarm 02-91, t1)
↔
11
Retry operation (by alarm 02-e1)
↔
1
Retry operation (by alarm 02-h1)
↔
1
Retry operation (by alarm 51, 52, 53, 54)
↔
1
Retry operation (by alarm 04, 06)
(Flickering)
Initializing electronic expansion valve
Fan manual operation
Содержание RHUE-3AVHN
Страница 1: ...Air to water Heat pump RHUE 3AVHN RHUE 4AVHN RHUE 5A V HN RHUE 6A V HN YUTAKI SERIES RHUE A V HN ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 16: ......
Страница 34: ......
Страница 70: ......
Страница 166: ......
Страница 236: ...Spare parts Service Manual 234 Spare parts of Yutaki SMGB0066 rev 0 12 2009 8 2 2 DHWT Domestic Hot Water Tank ...
Страница 238: ......
Страница 260: ......
Страница 261: ......
Страница 262: ...SMGB0066 rev 0 12 2009 Printed in Spain ...