205
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Alarm code
description
Activation of protection for inverter instantaneous over current (1)
• The alarm code is displayed on the PCB´s display.
• The compressor stops and restarts automatically in 3 minutes.
• The alarm appears after 6 retries during 30 minutes.
– This alarm code is displayed when the compressor current is higher than the set value. Totally 3 minutes during 10
minutes.
retry code: P-17
Replace ISPM or Dip-IPM
No
Yes
Is the current value
which activating ,more
than setting value (47.2A)?
Yes
(Inverter components are normal.)
No
(Lower than setting value)
Is discharge pressure excessively high?
Check discharge, suction pressure and
refrigerant cycle status
Check clogging of air-side heat exchanger
Check Fan
Install ISPM or Dip-IPM
correctly
No
Yes
Replace ISPM or Dip-IPM
Restart the operation
Check ISPM or Dip-IPM?
Check ISPM or Dip-IPM
correctly installed?
caution
Electrical hazard. Risk of electrical shock. Before checking and replacing the inverter parts perform the high
-
voltage discharge procedure by referring to section "Checking procedure for main parts".
Содержание RHUE-3AVHN
Страница 1: ...Air to water Heat pump RHUE 3AVHN RHUE 4AVHN RHUE 5A V HN RHUE 6A V HN YUTAKI SERIES RHUE A V HN ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 16: ......
Страница 34: ......
Страница 70: ......
Страница 166: ......
Страница 236: ...Spare parts Service Manual 234 Spare parts of Yutaki SMGB0066 rev 0 12 2009 8 2 2 DHWT Domestic Hot Water Tank ...
Страница 238: ......
Страница 260: ......
Страница 261: ......
Страница 262: ...SMGB0066 rev 0 12 2009 Printed in Spain ...