109
Technical data
SMGB0066 rev.0 - 12/2009
Controller pack
Service Manual
4
4.13. TECHnICAl dATA
4.13.1. System Controller (xEK23232 A)
Power supply
10%, -15%, 50Hz
Power Consumption
Max 5VA
Ambient operating
Temperature
0 to 50°C
Storage Temperature
-20 to 55°C
Humidity
0 to 90% RH non-condensing
dimensions
121 x 161.5 x 46mm (WxHxD)
Material Base
PA-GF 25-FR
Material Cover
PC-FR (VO certified)
degree of Protection
IP20 (IP30 with cable glands)
fire Class
V0
Protection class
Class I (according to EN60730-1)
Emissions Standards
Complies with EN61000-6-3
Immunity Standards
Complies with EN61000-6-1
Safety Standards
Complies with EN60730-1:2007
CE Compliance
93/68/EEC
WEEE Compliance
2002/96/EC
roHS Compliance
2002/95/EC
Heat Pump Control Signal
0-20mA, (max 10V @ 20mA), cable length max 20m (with wire cross-section 0.5mm²)
Boiler output relay
Potential free contacts (24V-230Vac 0.5A)
dHW electric heater enable
output relay
Potential-free contacts (230Vac 1A)
All other output relays
230Vac 1A (3A total)
Tariff / Timer Input
Input for potential-free contact (rated 5Vdc, switching current 1mA)
Heat Pump fault Input
Input for potential-free contact (rated 5Vdc, switching current 100mA)
rf receiver connection
Serial communications according to OpenTherm® technical specification v2.3 (max 18V,
23mA, 1000 baud)
diagnostic Interface
I²C Bus Specification v2.1. An I²C to RS232 interface is required for connection to a PC.
4.13.2. Water Temperature Sensor (xEK35524 A)
Element Type
NTC 20k @ 25°C
Mounting
Insertion well, or strap-on pipe with provided metal clip
range, Precision
+5 to +90°C, +/-1K
Cable length
2m cable, 2 core. (max cable length 100m)
dimensions (cartridge)
6.5mm Ø, 50mm long
Protection class
IP62
4.13.3. outdoor Temperature Sensor (xEK35438 A)
Element Type
NTC 20k @ 25°C
Mounting
Outside wall mounting
range, Precision
-30 to +40°C, +/-1K
dimensions
95 x 65 x 70mm (HxWxD)
Housing
Plastic (ABS)
Electric Connection
Terminals for 2 x 1.5mm² cable
Cable length
Max 100m
Protection Class
IP30
Содержание RHUE-3AVHN
Страница 1: ...Air to water Heat pump RHUE 3AVHN RHUE 4AVHN RHUE 5A V HN RHUE 6A V HN YUTAKI SERIES RHUE A V HN ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 16: ......
Страница 34: ......
Страница 70: ......
Страница 166: ......
Страница 236: ...Spare parts Service Manual 234 Spare parts of Yutaki SMGB0066 rev 0 12 2009 8 2 2 DHWT Domestic Hot Water Tank ...
Страница 238: ......
Страница 260: ......
Страница 261: ......
Страница 262: ...SMGB0066 rev 0 12 2009 Printed in Spain ...