12.7 Caution with the refrigerant leakage
The designers and the installers have the responsibility to follow the local codes and the local regulations that specify the
safety requirement against the refrigerant leakage.
12.7.1 Maximum permissible concentration of the HCFC gas
The refrigerant R410A, which is charged in the UTOPIA IVX/ES system, is an incombustible non-toxic gas. However, if the
leakage occurs and the gas fills a room, the gas may cause suffocation.
The maximum permissible concentration of the HCFC gas and the R410A in the air is 0.44 kg/m
³
, according to the
refrigeration and air conditioning system standard (KHK S 0010) by the KHK (high-pressure gas protection association) of
Japan. Therefore, you must take some effective measures in order to lower the R410A concentration in the air below 0.44
kg/m
3
, if there is a leakage.
12.7.2 Calculation of the refrigerant concentration
1
Calculate the total quantity of refrigerant R (kg) that is charged in the system that connects all the indoor units of the
rooms that need air conditioning systems.
2
Calculate the room volume V (m
³
) of each room.
3
Calculate the refrigerant concentration C (kg/m
³
) of the room according to the following equation:
C = R/V
R: Total quantity of charged refrigerant (kg)
V: Room volume (m
³
)
C: Refrigerant concentration (
≤
0.44* kg/m
3
for the R410A)
* Use this value only for reference because this value is not fixed yet.
12.7.3 Countermeasure for the refrigerant leakage according to the KHK standard
According to the KHK standards, you should arrange the facility as follows so that the refrigerant concentration will be bellow
0.3 kg/m
3
.
1
Provide a shutterless opening that will allow the fresh air to circulate into the room.
2
Provide a doorless opening with a size of 0.15% or more to the floor area.
3
Provide a ventilator, which must be linked with a gas leak detector, with a ventilating capacity of 0.5 m
3
/min or more per
Japanese refrigeration ton (=compressor displacement 8.5 m
3
/h of the air conditioning system which uses the
refrigerant).
•
IVX
O.U. model
Ton
RAS-8HRNM
2.49
RAS-10HRNM
3.32
RAS-12HRNM
4.15
•
ES
O.U. model
Ton
RAS-(2-2.5)HVRN1(E)
0.88
RAS-3HVRNS
1.14
RAS-4HVRNS1E
1.67
RAS-(5-6)HVRNS1E
2.27
RAS-8HRNSE
2.49
RAS-10HRNSE
3.32
4
Pay a special attention to the place, such as a basement and others, where the refrigerant may stay, because the
refrigerant is heavier than the air.
12 Maintenace notes
464
SMGB0060 rev. 1- 12/2010
Содержание RAS-10HRNM
Страница 2: ......
Страница 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Страница 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Страница 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Страница 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Страница 120: ...4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN1 E 4 Electrical Wiring 112 SMGB0060 rev 1 12 2010 ...
Страница 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Страница 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Страница 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Страница 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Страница 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Страница 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Страница 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Страница 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Страница 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Страница 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Страница 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Страница 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Страница 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Страница 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Страница 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Страница 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Страница 334: ...9 1 Spare parts for IVX Series RAS 3HVRNME Cycle and structural parts 9 Spare Parts 326 SMGB0060 rev 1 12 2010 ...
Страница 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Страница 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Страница 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Страница 353: ...RAS 4 6 HVRNS1E Cycle structural and electrical parts 9 Spare Parts 345 SMGB0060 rev 1 12 2010 9 ...
Страница 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Страница 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Страница 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Страница 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Страница 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Страница 481: ......