Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
The Comp. does not stop
or start even if the setting
temperature on the LCD
changes to *3)
Failure of air inlet
thermistor
Failure of thermistor
Check it by self-checking *2)
Replace or correctly connect the
wires if Abnormal Operation
exists
Disconnection of
thermistor
Abnormal operation of the remote control switch
cord
Failure of the indoor unit PCB
Check PCB by means of the self-
check mode *1)
Replace PCB if it failed
Incorrect optional setting
Check the setting condition of
"remote control thermostat" by
means of the optional setting
Setting and control:
"00": Control by means of the
indoor thermistor for the suction
air
"01": Control by means of the
thermostat of the remote control
switch
"02": Control by means of the
average value of the indoor
thermistor for the suction air and
the thermostat of the remote
control switch
If the thermostat of the remote
control switch is not used, set at
"00"
Incorrect Input/Output setting
Check setting condition of “i1”
and “i2” by Input/Output setting.
* Setting and Control:
“01”: Room thermostat (Cooling)
“02”: Room thermostat (Heating)
In case that room thermostat is
not used, set for input signal
actually used. If no signal is used,
set at “00”
Indoor fan speed does
not change
Failure of the Discharge
Air Temp. Thermistor
Failure of the Thermistor
Check the Thermistor by means
of the self-check mode *2)
Replace or Correctly connect the
wiring when it is abnormal
Disconnected Wire of
the Thermistor
Failure of the Remote Control Switch
Check it by means of the self-
check mode *1)
Replace if it failed
Failure of PCB for the indoor unit
Replace if PCB fails
No defrost operation
mode is available during
the heating process or
the defrost operation
continues
Failure of thermistor for
outdoor evaporating
temp. during heating
Failure of thermistor
Replace or correctly connect when it is abnormal
Disconnected wire of
thermistor
Failure of 4-way valve
Disconnected 4-way
valve coil
Measure the resistance of coil
Replace the 4-way valve
Incorrect activation of 4-
way valve
Enforced power supply
Disconnected control wires between indoor unit and
outdoor unit
Check the connectors
Correctly connect the wiring
Failure of the outdoor
units of PCB
Disconnected wiring to
PCB
Check the connectors
Correctly connect the wiring
Failure of PCB
Check PCB by means of the self-
check mode *1)
Replace PCB when the check
mode is not available
Failure of the Indoor Unit
of PCB
Disconnected wiring to
PCB
Check the connectors
Correctly connect the wiring
Failure of the PCB
Check PCB by means of the self-
check mode *1)
Replace if PCB fails
The LED and the LCD on
the remote control switch
remain ON
Failure of PCB in the indoor unit or the remote
control switch
8 Troubleshooting
199
SMGB0060 rev. 1- 12/2010
8
Содержание RAS-10HRNM
Страница 2: ......
Страница 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Страница 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Страница 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Страница 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Страница 120: ...4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN1 E 4 Electrical Wiring 112 SMGB0060 rev 1 12 2010 ...
Страница 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Страница 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Страница 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Страница 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Страница 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Страница 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Страница 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Страница 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Страница 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Страница 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Страница 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Страница 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Страница 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Страница 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Страница 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Страница 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Страница 334: ...9 1 Spare parts for IVX Series RAS 3HVRNME Cycle and structural parts 9 Spare Parts 326 SMGB0060 rev 1 12 2010 ...
Страница 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Страница 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Страница 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Страница 353: ...RAS 4 6 HVRNS1E Cycle structural and electrical parts 9 Spare Parts 345 SMGB0060 rev 1 12 2010 9 ...
Страница 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Страница 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Страница 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Страница 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Страница 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Страница 481: ......