Check list on compressor
CLIENT:
MODEL:
DATE:
Serial No.:
Production date:
Checker:
N°
Check item
Check method
Result
Remarks
1
Is THM9 correctly connected?
THM9: Discharge gas thermistor
(1) Is wire of thermistor correctly connected by
viewing?
(2) Check to ensure the 7-segment indication of
Td when comp. is operating.
Td: Temperature of THM9
2
Is thermistor THM9 disconnected?
(1) Check to ensure that thermistor on the top of
comp. is correctly mounted by viewing?
(2) Check to ensure that actually measured
temp. is the same as the indication during check
mode.
3
Is current sensor faulty?
(1) Check to ensure that indication A1 and A2
are 0 during compressor stopping.
(2) Check to ensure that indication A1 and A2
are not 0 during compressor running.
4
Is current sensing part on PCB2
faulty?
5
Is the direction of current sensor
(CTU, CTV) reverse?
Check the direction => by viewing.
6
Are power source wires, U and V
inserted correctly into current
sensor?
Check to ensure that wires are correctly
inserted.
7
Is exp. valve (MV1) correctly
connected?
Check to ensure that MV1 to CN5A is correctly
connected.
8
Is exp. valve (MV1) coil correctly
connected?
Check to ensure that each coil is correctly
mounted on the valve.
9
Are the refrigeration cycle and
electrical wiring system incorrectly
connected?
Check to ensure that refrigerant is flowing into
indoor units by operating one refrigerating cycle
only from the outdoor unit.
10
Is opening of exp. valve completely
closed (locked)?
Check the following by the check mode of
outdoor units.
(1) Liquid pipe temp. (TL) < air intake temp.
(Ti) during cooling operation
(2) Liquid pipe temp. (TL) > air intake temp.
(Ti) during heating operation
11
Is opening of exp. valve fully opened
(locked)?
Check to ensure that liquid pipe temp. is lower
than air intake temp. of stopping indoor unit
when other indoor units are operating under
cooling operation
12
Are the contacts for comp. magnetic
switch CMC1 faulty?
Check the surface of each contact (L1, L2 and
L3) by viewing.
13
Is there any voltage abnormality
among L1-L2, L2-L3 and L3- L1?
Check to ensure that voltage imbalance is
smaller than 3%. Please note that power source
voltage must be within 380 V or 220 V+10%.
14
Is the comp. oil acidified during
compressor motor burning?
Check to ensure that the oil color is not black.
7 Test Run
193
SMGB0060 rev. 1- 12/2010
7
Содержание RAS-10HRNM
Страница 2: ......
Страница 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Страница 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Страница 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Страница 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Страница 120: ...4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN1 E 4 Electrical Wiring 112 SMGB0060 rev 1 12 2010 ...
Страница 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Страница 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Страница 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Страница 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Страница 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Страница 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Страница 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Страница 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Страница 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Страница 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Страница 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Страница 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Страница 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Страница 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Страница 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Страница 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Страница 334: ...9 1 Spare parts for IVX Series RAS 3HVRNME Cycle and structural parts 9 Spare Parts 326 SMGB0060 rev 1 12 2010 ...
Страница 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Страница 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Страница 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Страница 353: ...RAS 4 6 HVRNS1E Cycle structural and electrical parts 9 Spare Parts 345 SMGB0060 rev 1 12 2010 9 ...
Страница 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Страница 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Страница 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Страница 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Страница 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Страница 481: ......