Checking procedure for the compressor
CHECK LIST ON COMPRESSOR
Client:
Model:
Date:
Serie No.
Production Date:
Checker:
No.
Check item
Check method
Result
Remarks
1
Is THM9 correctly connected?
THM9: Discharge Gas
Thermistor
1. Is wire of thermistor correctly connected by
viewing?
2. Check to ensure the 7-segment indication of
Td when comp. is operating.
Td: Temperature of THM9
2
Is thermistor THM9
disconnected?
1. Check to ensure that thermistor on the top of
comp. is correctly mounted by viewing?
2. Check to ensure that actually measured temp.
is the same as the indication during check mode.
3
Is current sensor faulty?
1. Check to ensure that indication A1 and A2 are
0 during compressor stopping.
2. Check to ensure that indication A1 and A2 are
not 0 during compressor running.
4
Is current sensing part on
PCB2 faulty?
5
Is the direction of current
sensor CTU, CTV) reverse?
Check the direction => by viewing.
6
Are power source wires, U and
V inserted correctly into
current sensor? .
Check to ensure that wires are correctly inserted
7
Is exp. valve (MV1) correctly
connected?
Check to ensure that MV1 to CN5A is correctly
connected
8
Is exp. valve coil (MV1)
correctly connected?
Check to ensure that each coil is correctly
mounted on the valve.
9
Are the refrigeration cycle and
electrical wiring system
incorrectly connected?
Check to ensure that refrigerant is flowing into
indoor units by operating one refrigerating cycle
only from the outdoor unit.
10
Is opening of exp. valve
completely closed (locked)?
Check the following by the check mode of outdoor
units.
1. Liquid Pipe Temp. (TL) < Air Intake Temp. (Ti)
during Cooling Operation
2. Liquid Pipe Temp. (TL) > Air Intake Temp. (Ti)
during Heating Operation
11
Is opening of exp. valve fully
opened locked)?
Check to ensure that liquid pipe temp. is lower
than air intake temp. of stopping indoor unit when
other indoor units are operating under cooling
operation.
12
Are the contacts for comp.
magnetic switch CMC1 faulty?
Check the surface of each contact (L1, L2
and L3) by viewing.
13
Is there any voltage
abnormality among L1-L2, L2-
L3 and L3-L1?
Check to ensure that voltage imbalance is
smaller than 3%.
Please note that power source voltage must be
within 380V or 220V+10%.
14
Is the comp. oil acidified during
compressor motor burning?
Check to ensure that the oil color is not black.
8 Troubleshooting
311
SMGB0060 rev. 1- 12/2010
8
Содержание RAS-10HRNM
Страница 2: ......
Страница 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Страница 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Страница 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Страница 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Страница 120: ...4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN1 E 4 Electrical Wiring 112 SMGB0060 rev 1 12 2010 ...
Страница 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Страница 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Страница 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Страница 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Страница 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Страница 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Страница 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Страница 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Страница 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Страница 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Страница 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Страница 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Страница 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Страница 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Страница 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Страница 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Страница 334: ...9 1 Spare parts for IVX Series RAS 3HVRNME Cycle and structural parts 9 Spare Parts 326 SMGB0060 rev 1 12 2010 ...
Страница 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Страница 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Страница 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Страница 353: ...RAS 4 6 HVRNS1E Cycle structural and electrical parts 9 Spare Parts 345 SMGB0060 rev 1 12 2010 9 ...
Страница 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Страница 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Страница 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Страница 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Страница 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Страница 481: ......