Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Power failure or power is not ON
Measure the voltage by means of
the tester
Supply the power
Blown out fuse for the power source
or activation of the outdoor unit
breaker
Short-circuit between the wires
Check the insulation material for
breaks
Remove the short-circuit and
replace the fuse
Short-circuited wire to ground
Measure the insulation resistance
Remove short-circuit to ground and
replace the fuse
Faulty comp. motor
Measure the resistance between
the wires and the insulation
resistance
Replace the comp. and the fuse
Failure of outdoor unit fan motor
Measure resistance between wires
and insulation resistance
Replace the unit fan motor and the
fuse
Blown out fuse for control circuit or
activation of outdoor unit breaker
Short-circuit between the wires
Check the insulation material for
breaks
Remove the short-circuit and
replace the fuse
Short-circuit of the control circuit (to
ground)
Measure the insulation resistance
Remove the short-circuit and
replace the fuse
Faulty solenoid coil for the magnetic
switch for the comp. motor
Measure the resistance of coil
Replace the magnetic switch and
the fuse
Failure of outdoor unit fan motor
Measure the resistance between
the wires and the insulation
resistance
Replace the outdoor unit fan motor
and fuse
PCB1 Power circuit failure
PCB1 Measure output voltage *1)
Replace PCB1
Disconnected wires insufficient
contacting or incorrect connection
Between outdoor unit and indoor
unit
Check the continuity of the wires
Check for looseness of the
connection screws
Check the terminal Nos.
Replacing wires repairing and
tightening the Power source wiring
for the screws and the correct wiring
Power source wiring for the screws
and the correct wiring outdoor unit
Faulty PCB (outdoor unit, indoor
unit)
Disconnected wires to PCB
Check the connections
Correctly connect the wires
Faulty PCB
—
Replace PCB if faulty
Incorrect wiring
Disconnected wire; insufficient
contacting
Check the continuity and the
looseness of connection screws
Replacing wires, repairing and
tightening the screws
Incorrect wiring
Check the terminal Nos.
Correctly connect the wires
PCB1 output voltage
Voltage
Vcc 12 – GND2
12 VDC
Vcc 05 – GND1
5 VDC
Vcc 12 – GND1
12 VDC
Vcc 15 – GND1
15 VDC
Vcc 24 – GND1
24 VDC
Vcc 12T– GND1
12 VDC
8 Troubleshooting
217
SMGB0060 rev. 1- 12/2010
8
Содержание RAS-10HRNM
Страница 2: ......
Страница 4: ...Index ii SMGB0060 rev 1 12 2010 ...
Страница 56: ...2 Unit Installation 48 SMGB0060 rev 1 12 2010 ...
Страница 117: ...RAS 4 6 HVRNM1E 4 Electrical Wiring 109 SMGB0060 rev 1 12 2010 4 ...
Страница 118: ...RAS 4 6 HRNM1E 4 Electrical Wiring 110 SMGB0060 rev 1 12 2010 ...
Страница 120: ...4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN1 E 4 Electrical Wiring 112 SMGB0060 rev 1 12 2010 ...
Страница 121: ...RAS 3HVRNS 4 Electrical Wiring 113 SMGB0060 rev 1 12 2010 4 ...
Страница 122: ...RAS 4 6 HVRNS1E 4 Electrical Wiring 114 SMGB0060 rev 1 12 2010 ...
Страница 123: ...RAS 8 10 HRNSE 4 Electrical Wiring 115 SMGB0060 rev 1 12 2010 4 ...
Страница 124: ...4 Electrical Wiring 116 SMGB0060 rev 1 12 2010 ...
Страница 145: ...Dry operation Continues in the next page 5 Control System 137 SMGB0060 rev 1 12 2010 5 ...
Страница 147: ...Heating operation Continues in the next page 5 Control System 139 SMGB0060 rev 1 12 2010 5 ...
Страница 148: ...5 Control System 140 SMGB0060 rev 1 12 2010 ...
Страница 153: ...Activation for protection device control 5 Control System 145 SMGB0060 rev 1 12 2010 5 ...
Страница 162: ...Activation for protection device control 5 Control System 154 SMGB0060 rev 1 12 2010 ...
Страница 166: ...Preheating control of compressor 5 Control System 158 SMGB0060 rev 1 12 2010 ...
Страница 168: ...5 Control System 160 SMGB0060 rev 1 12 2010 ...
Страница 180: ...6 Optional functions 172 SMGB0060 rev 1 12 2010 ...
Страница 224: ...8 Troubleshooting 216 SMGB0060 rev 1 12 2010 ...
Страница 263: ...RAS 4 6 HVRNS1E 8 Troubleshooting 255 SMGB0060 rev 1 12 2010 8 ...
Страница 264: ...RAS 8 10 HRNSE 8 Troubleshooting 256 SMGB0060 rev 1 12 2010 ...
Страница 269: ...RAS 8 10 HRNSE 8 Troubleshooting 261 SMGB0060 rev 1 12 2010 8 ...
Страница 334: ...9 1 Spare parts for IVX Series RAS 3HVRNME Cycle and structural parts 9 Spare Parts 326 SMGB0060 rev 1 12 2010 ...
Страница 337: ...RAS 4 6 HVRNM1E Cycle and structural parts 9 Spare Parts 329 SMGB0060 rev 1 12 2010 9 ...
Страница 340: ...RAS 4 6 HRNM1E Cycle and structural parts 9 Spare Parts 332 SMGB0060 rev 1 12 2010 ...
Страница 342: ... Electrical parts 9 Spare Parts 334 SMGB0060 rev 1 12 2010 ...
Страница 353: ...RAS 4 6 HVRNS1E Cycle structural and electrical parts 9 Spare Parts 345 SMGB0060 rev 1 12 2010 9 ...
Страница 354: ... Electrical parts 9 Spare Parts 346 SMGB0060 rev 1 12 2010 ...
Страница 356: ...RAS 8 10 HRNSE Cycle and structural 9 Spare Parts 348 SMGB0060 rev 1 12 2010 ...
Страница 359: ... Electrical parts 9 Spare Parts 351 SMGB0060 rev 1 12 2010 9 ...
Страница 440: ...10 Servicing 432 SMGB0060 rev 1 12 2010 ...
Страница 464: ...11 Electrical checks of main parts 456 SMGB0060 rev 1 12 2010 ...
Страница 481: ......