– 136 –
How to run the product with the outdoor unit test switch
1. Turn off the power, wait for at least 10 seconds, and turn the power back on.
2. Turn on the indoor unit power relay by using the "air purification" button on the remote control unit.
Then ensure that the outdoor unit will be energized.
3. Detach the electrical parts lid from the outdoor unit and ensure that the "LD301" is blinking
once.
4.
Pressing the test switch for 1 second or more will cause the "LD303" to go on and will start forcible
cooling.
※
(Initialization of the expansion valve may take about 1 minute to start.)
5. Pressing the "test switch" again for 1 second or more will stop the product.
1. Turn on the outdoor terminal boards A and B (220 V AC).
2. Detach the electrical parts lid from the outdoor unit and ensure that the "LD301" is blinking
once.
3.
Pressing the test switch for 1 second or more will cause the "LD303" to go on and start the forcible
cooling.
※
(Initialization of the expansion valve may take about 1 minute to start.)
4. Pressing the "test switch" again for 1 second or more will stop the product.
1) When you are obliged to start the product on the outdoor unit side for the purpose of servicing
2) If the indoor electrical parts is out of order and if you wish to run the outdoor unit
※
Cautions
1. Applying power directly to the outdoor unit will cause a rush current to stress the outdoor unit.
Therefore, if the indoor unit is not out of order, do not use the method descried in 2).
2. Before making the connections, be sure to turn off the breaker.
3. Do not under any circumstances run the product for more than 5 minutes.
4. Doing work with the compressor connector removed will cause the LD301 to blink 4 times.
It will not start.
5. For another test run, turn off the breaker and turn it back on. (The test switch is accepted only
once after power-on. After operation by remote control, it is not accepted.)
6. When the operation with the test switch is over, turn off the breaker and set the connectors back.
2A-FUSE
3.15A-FUSE
DC VOLTAGE MEASURING POINT(-)(IPM 33)
DC VOLTAGE MEASURING POINT(+)(IPM 25)
COMPRESSOR CONNECTOR(CN1)
CONNECTOR(CN24)
OUTDOOR FAN
IPM
MAIN P.W.B
SELF-CHECK CONNECTOR(CN30)
LD301
LD302
LD303
TEST SWITCH
LD301(RED)
LD302(RED)
LD303(RED)
TEST SWITCH
黑
棕
蓝
SELF-CHECK CONNECTOR(CN30)
OUTDOOR FAN CONNECTOR(CN24)
DC VOLTAGE MEASURING POINT(-)(IPM N)
DC VOLTAGE MEASURING POINT(+)(IPM P)
RAC-10SH3
、
RAC-14SH3
RAC-18SH3
Содержание RAC-10SH3
Страница 57: ... 55 MODEL RAC 18SH3 Unit mm 580 5 600 345 299 19 5 ...
Страница 60: ... 8 5 WIRING DIAGRAM MODEL RAS 10SH3 3 H S 4 1 S A R 3 H S 8 1 S A R INDOOR UNIT ...
Страница 62: ... 0 6 MODEL RAC 18SH3 OUTDOOR UNIT WHT YEL RED INDOOR UNIT ...
Страница 64: ... 2 6 3 H S 8 1 S A R 3 H S 4 1 S A R 3 H S 0 1 S A R L E D O M ...
Страница 150: ... 8 4 1 MODEL RAC 18SH3 ...
Страница 153: ...HHAW NO 0060E RAS 10SH3 RAC 10SH3 RAS 14SH3 RAC 10SH3 RAS 18SH3 RAC 18SH3 ...