4
P5416904
Software Overview
This system, which connects by H-LINK the following models, performs controlling and monitoring of the air
conditioning unit via the computer connected by LAN.
Item
Specification
Maximum Number of
Connectable Units
Outdoor Units: 64 units
(Refrigerant System setting range 0 to 63)
Indoor Unit: 160 units
Total Number: 200 units *1
Central Controller used in
combinations *2 *3
PSC-A128WX2, PSC-A64S, PSC-A16RS, PSC-A32MN
NOTE:
When connecting the facility unit with control and monitor using the External Input/Output function, refrigerant
systems 62 and 63 cannot be used.
*1: The number for total equipment is the total of Outdoor unit, Indoor unit, Central Controller and facility unit
which performs controlling and monitoring by using Input/Output function.
*2: The total number of Central Controllers which can be combined with this unit will be eight units.
*3: The Indoor Unit without a wired controller cannot be connected.
Содержание PSC-A128WEB3