Appendix D:
94
Appendix D:
Restoring Factory Default Settings
Keypad Method
– You can restore (initialize) all inverter parameters to factory default
settings from the keypad. (The network method via DeviceNet is on the next page.) After
initializing the inverter, use the powerup test in to get the motor running again.
No.
Action
Display
Func./Parameter
1
Use the
,
, and
keys to
navigate to the “B” Group.
“B” Group selected
2
Press the
key.
First “B” parameter selected
3
Press and hold the
key until ->
Country code for initialization
selected
4
Press the
key.
00 = Japan, 01 = Europe,
02 = U.S.
5
Confirm the country code is correct. Do not change it unless you are absolutely sure the
power input voltage range and frequency match the country code setting.
To change the country code, press
or
to set,
to store.
6
Press the
key.
Country code for initialization
selected
7
Press the
key.
Initialization function selected
8
Press the
key.
00 = initialization disabled,
clear trip history only
9
Press the
key.
00 = clear trip history
01 = initialize all settings
10
Press the
key.
Initialization now enabled to
restore all defaults
11
Press and hold the
,
, and
keys. Do not release yet.
First part of special key
sequence
12
Holding the keys above, press and
hold the
(STOP) key for 3 sec.
Final part of special key
sequence
13
Release only the
(STOP)
key;
wait for
d
0 0
blinking display.
Initialization begins when
display starts blinking
14
Now release the
, ,
and
keys only after the
d
0 0
display
function begins blinking.
Default parameter country code
shown during initialization
process (left-most char displays
alternating pattern)
15
Initialization is complete.
Function code for output
frequency monitor shown
FUNC.
1
2
b
- -
FUNC.
b
0 1
1
b
8 5
FUNC.
0 2
1
2
STR
FUNC.
b
8 5
2
b
8 4
FUNC.
0 0
1
0 1
STR
b
8 4
FUNC.
1
2
b
8 4
STOP
RESET
b
8 4
STOP
RESET
d
0 0
FUNC.
1
2
E U
U S A
J P
d
0 1