Network Register Map
80
“F” Group Parameters and
Basic Inverter Data
DeviceNet Class ID = 100
Func.
Code
Name
Inst Attr Size
Range
Scaling
Get/
Set
F_01
Output frequency setting
1
159
2
0 – 360Hz
100
Get
F_02
Acceleration (1) time setting
1
160
2
0.1 – 3000.0 sec.
10
Get
F_03
Deceleration (1) time setting
1
161
2
0.1 – 3000.0 sec.
10
Get
F_04
Keypad Run key routing
1
162
1
0 forward
1 reverse
2 [F/R] terminal
—
Get
—
Input terminal functions monitor1
1
163
2
See EDS file
—
Get
—
Input terminal functions monitor2
1
164
2
See EDS file
—
Get
—
Input terminal functions setting1
1
165
2
See EDS file
—
Get
—
Input terminal functions setting2
1
166
2
See EDS file
—
Get
—
Output terminal functions
monitor
1
167
1
See EDS file
—
Get
Supported Services, DeviceNet Class ID = 100
Service Name
Code
Description
Reset
05h
Initializes all parameters to factory default values,
excluding P_41 DeviceNet baud rate and P_42
DeviceNet MAC ID
Get_Attribute_Single
0Eh
Set_Attribute_Single
10h
Содержание L100DN DeviceNet Series Addendum
Страница 96: ......