![Hitachi L100DN DeviceNet Series Addendum Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/hitachi/l100dn-devicenet-series-addendum/l100dn-devicenet-series-addendum_read-this-first-manual_142290031.webp)
L100DN Inverter
31
Operations and Monitoring
This section covers new or modified intelligent terminal functions for L100DN
DeviceNet Series inverters, corresponding to Chapter 4, “Operations and Monitoring,” in
the L100 Inverter Instruction Manual.
Example Wiring Diagram
The L100DN DeviceNet Series inverters have fewer intelligent I/O terminals and are
without analog I/O and relay outputs, in comparison to the standard L100 inverters. An
example wiring diagram for L100DN is shown below. The DeviceNet interface wiring is
discussed in detail in “Step 2 – Connect Network Devices” on page 43.
12
11
1
2
3
L
D
CL
V+
CM2
L100DN
P24
Open collector outputs
CANbus High
Power source,
3-phase or
1-phase, per
inverter model
R
(L1)
S
(L2)
T
N(L3)
U
(T1)
V
(T2)
W
(T3)
Motor
[FW]
[STP]
Intelligent inputs,
3 terminals
CANbus Low
Drain
NOTE:
For the wir-
ing of intelligent I/O,
be sure to use
twisted pair /
shielded cable.
Attach the shield wire
for each signal to its
respective common
terminal at the
inverter end only.
Bus supply –
Load
Alarm signal
Run signal
Load
+
–
Logic output common
Input
circuits
[3] configurable
discrete inputs
Logic input common
+
–
24V
+1
+
–
Braking
unit
(optional)
DC reactor
(optional)
Output
circuits
Breaker,
MCCB or GFI
V–
CH
Bus
DeviceNet interface
(Bare)
(Red)
(White)
(Blue)
(Black)
[EXT]
Содержание L100DN DeviceNet Series Addendum