Chapter 5 Instruction Specifications
5-36
Item number
Basic instructions-27
Name
Counter clear (COUNTER CLEAR)
Ladder format
Condition code
Processing time (
µ
s)
Remark
R7F4
R7F3
R7F2
R7F1
R7F0
Average Maximum
DER
ERR
SD
V
C
CL n
z
z
z
z
z
Instruction format
Number of steps
0.9
Condition
Steps
OUT CL n s
—
1
Bit
Word
Double word
Usable I/O
X
Y
R,
M
TD, SS,
CU, CT
WX WY
WR,
WM TC DX DY
DR,
DM
C
o
nstant
Other
n
Counter number
{
0 to 255 (Decimal)
Function
•
Clears the progress values of the integral timer and switches off the timer coil.
•
In the case of WDT, the time monitor check is performed (see WDT for details).
•
In the case of counters, the progress value is cleared and the counter coil is switched off.
•
The clearing operation is conducted immediately before execution of the counter or timer coil instruction indicated by the
clear coil.
Example:
X00000
CL10
X00001
CU10
X00002
CL10
1) When X00000 is turned on, the CL10 immediately prior to CU10, and CU10
is cleared.
2) Even if X00002 turns on, if X00001 is off, the CL10 is turned off by the
circuit before CU10 is executed. Thus, the CU10 will not be cleared.
Notes
•
The same number should be used for the timer number and counter number.
O
U
T
CL
n
s
Содержание HIDIC MICRO-EH
Страница 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Страница 12: ...MEMO ...
Страница 14: ...Chapter 1 Features 1 2 MEMO ...
Страница 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Страница 196: ...Chapter 5 Instruction Specifications 5 146 ...
Страница 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...