Chapter 3 Function and Performance Specifications
3-6
3.3
Performance Specifications
3.3.1
Calculation Specifications
The calculation specifications of the PLC are described below.
Model
Name
10-point type
14-point type
23/28-point type
Type
EH-D10DT
EH-D10DTP
EH-D10DR
EH-D14DT
EH-D14DTP
EH-A14DR
EH-D14DR
EH-A14AS
EH-A23DRP
EH-A23DRT
EH-D23DRP
EH-D28DT
EH-D28DTP
EH-A28DRP
EH-A28DRT
EH-A28DR
EH-D28DRP
EH-D28DRT
EH-D28DR
EH-A28AS
CPU
32-bit RISC processor
Processing system
Stored program cyclic system
Basic instructions
0.9
µ
s / instruction
Control
specifications
Processing
speed
Application instructions
Several 10
µ
s / instruction
User program memory
3 k steps max. (FLASH memory)
Instruction
language
Basic instructions
39 types such as LD, LDI, AND, ANI, OR, ORI, ANB, ORB, OUT, MPS,
MRD, MPP, etc.
Operation
processing
specifications
Arithmetic instructions
Application instructions
62 types (arithmetic, application, control, FUN command etc.)
Ladder
Basic instructions
39 types, such as
Arithmetic instructions
Application instructions
62 types (arithmetic, application, control, FUN command etc.)
I/O processing system
Refresh processing
I/O
processing
specifications
External
I/O
Maximum number of
points
10 points
126 points
135 points
140 points
Bit
1,984 points (R0 to R7BF)
Internal
output
Word
4,096 words (WR0 to WRFFF)
Bit
64 points (R7C0 to R7FF)
Special
Word
512 words (WRF000 to WRF1FF)
Bit/word shared
16,384 points, 1,024 words (M0 to M3FFF, WM0 to WM3FF)
Number of points
256 points (TD + CU) *1
Timer
counter
Timer set value
0 to 65,535, timer base 0.01 s, 0.1 s, 1 s (0.01s has maximum 64 points *2)
Counter set value
1 to 65,535 times
Edge detection
512 points (DIF0 to DIF511: Decimal)
+ 512 points (DFN0 to DFN511: Decimal)
Program system
Instruction language, ladder diagram
Peripheral
equipment
Peripheral unit
Programming software
(LADDER EDITOR DOS version/Windows® version, Pro-H)
Instruction language programmer and form graphic display programmer cannot
be used.
Maintenance
functions
Self-diagnosis
PLC error (LED display): Microcomputer error, watchdog timer error, memory
error, program error, system ROM/RAM error, scan time monitoring, battery
voltage low detection, etc.
*1:
The same numbers cannot be used with the timer counter.
*2:
Only timers numbered 0 to 63 can use 0.01 s for their timer base.
Содержание HIDIC MICRO-EH
Страница 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Страница 12: ...MEMO ...
Страница 14: ...Chapter 1 Features 1 2 MEMO ...
Страница 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Страница 196: ...Chapter 5 Instruction Specifications 5 146 ...
Страница 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...