Figure 8-76 Typical FL-net System Power Supply Wiring and Grounding
8.7.3 Power supply wiring and grounding for FL-net system network devices
Figure 8-77 shows a typical power supply wiring/grounding scheme for the network devices of the
FL-net system.
When making power supply wiring and ground connections, observe the following instructions:
• Connect the ground terminal on a coaxial cable to the Class D ground that is dedicated to the
controller.
• Connect the frame ground of the 10BASE-T hub to the Class D ground that is dedicated to the
controller. Also, ensure that the 10BASE-T hub receives power from the same insulating
transformer with a static shield as for the controller power supply.
• Do not connect the controller’s FG (frame ground) terminal to the frame of the control panel.
Provide the controller with dedicated Class D or higher grounding.
• Connect the FG (frame ground) terminal on the FL.NET module to the FG (frame ground)
terminal on the controller.
• Connect the shield ground of the transceiver (AUI) cable to the FG (frame ground) terminal on the
FL.NET module.
Pre-
operational
Ry circuit
H
L
LG
FG
100 VAC
Control
power
supply
Distribution
switchboard
Controller control
panel
Class D
grounding
Class D
grounding
Panel ground
(5.5 mm
2
or more)
Controller ground
(5.5 mm
2
or more)
PLC, etc.
Class D
grounding
Panel ground
Содержание FL.NET
Страница 1: ......
Страница 2: ......
Страница 29: ...1 OVERVIEW ...
Страница 33: ...2 FL NET MODULE ...
Страница 42: ...3 FL NET MODULE INSTALLATION ...
Страница 46: ...4 FL NET MODULE WIRING PROCEDURES ...
Страница 53: ...5 USER GUIDE ...
Страница 203: ...5 USER GUIDE 5 151 Sample printout ...
Страница 206: ...6 MAINTENANCE ...
Страница 210: ...7 TROUBLESHOOTING ...
Страница 225: ...8 APPENDIXES ...