5 USER GUIDE
5-67
Parameter Input
range
Message transmission service number 5 (only when a mathematical/logical function is
used)
Remote node number
1 to 254
Error code storage address
Read parameter data storage address
Specify a real address (even-numbered address)
on the CPU or CMU.
(*) For the relationship between real address on LPU (memory address) and symbol name
such as XW000, see “Table 2-5 Virtual Address Spare and Symbol Names.”
“Memory address” in table is the address to be specified.
[Return code] (for C mode handler only)
0 (0x00000000): Normal termination
-1 (0xFFFFFFFF): Parameter abnormality exists or the handler is busy processing another
message. Error code is stored in area which specified error code storage
address. For content and measure of error code, see “Table 7-7 List of
Detectable Codes.”
-2 (0xFFFFFFFE): When mounting S10V, specifies real address (0x01000000 to 0xFFFFFFFE)
on CMU at error code storage address or read parameter data storage
address. Please review the specified address.