8 APPENDIXES
8-71
• If the transceiver (AUI) needs power supply from a DC power source (12 VDC, etc.), furnish the
network with a dedicated regulated power supply and connect its DC output to the specified
terminal on the FL.NET module. The required 100 VAC input power must be supplied from the
same insulating transformer with a static shield as for the controller.
Figure 8-77 Typical Power Supply Wiring/Grounding Scheme for
FL-net System Network Devices
100 VAC
Coaxial cable
Transceiver
Ground terminal
Hub
Transceiver cable
(AUI cable)
Insulating
transformer with
static shield
Class D grounding
12-VDC power
supply for AUI
Class D
grounding
dedicated to
controller
100 VAC