[Function]
• When the node having a specified node number is to be subjected to common memory
transfer, an offset size will be reported to the FL.NET module.
• If the specified node number coincides with the self-node number, a parameter error occurs.
• If the maximum size (0x200) of common memory area 1 is exceeded by the offset size
specified for common memory area 1, a parameter error occurs.
• If the maximum size (0x2000) of common memory area 2 is exceeded by the offset size
specified for common memory area 2, a parameter error occurs.
• If you specify the offset size during message processing, a “message processing already in
progress” error occurs.
When an offset size is specified for a specific node number, it is stored in
memory until the FL.NET module is turned OFF or reset. Note, however, that
the user cannot reference the offset setting within the FL.NET module after
completion of offset setup. The offset setting must be managed by the user.
The above feature is designed for use in cases where the available memory
space of the S10mini or S10V is insufficient. It is recommended that you do
not use the feature when the memory space of the S10mini or S10V is
adequate.
When the address limit of common memory area 1 or 2 is exceeded by the
application of an offset, the resulting excess portion of address data will not
transfer to the S10mini or S10V memory. Exercise care not to exceed the
limits of the common memory areas.
Содержание FL.NET
Страница 1: ......
Страница 2: ......
Страница 29: ...1 OVERVIEW ...
Страница 33: ...2 FL NET MODULE ...
Страница 42: ...3 FL NET MODULE INSTALLATION ...
Страница 46: ...4 FL NET MODULE WIRING PROCEDURES ...
Страница 53: ...5 USER GUIDE ...
Страница 203: ...5 USER GUIDE 5 151 Sample printout ...
Страница 206: ...6 MAINTENANCE ...
Страница 210: ...7 TROUBLESHOOTING ...
Страница 225: ...8 APPENDIXES ...