Appendix
137/142
netPLC C100 | Startup Guide
DOC090701UM02EN | Revision 2 | English | 2009-10 | Released | Public
© Hilscher, 2009
Abbildung 16: PROFIBUS Network
Up to 32 PROFIBUS devices can be connected to one bus segment. If
several bus segments are linked to each other with repeaters, there can be
up to 127 devices on the network.
The maximum length of a bus segment depends on the baud rate used.
Only PROFIBUS certified cable, preferably the cable type A, should be
used.
Baud rate in
kBit/s
Max. distance
9,6 1.200
m
19,2 1.200
m
93,75 1.200
m
187,5 1.000
m
500
,0
400
m
1.500
,0
200
m
3.000
,0
100
m
6.000
,0
100
m
12.000
,0
100
m
Table 34: PROFIBUS Segment Length in dependence of the Baud rate
Parameter Value
Impendance 135…165
Ohm
Capacity
< 30 pF/m
Loop resistance
110 Ohm/km
Wire gauge
0,64 mm
Table 35: Characteristics of PROFIBUS certified Cable