18.4 Memory Card
The slot PLC “NPLC C100” device can be set back to factory settings with
a micro SD card and the base firmware on it.
Requirements
•
The memory card can have up to 4 GB storage capacity.
•
The memory card must be formatted in the FAT16 format (no FAT32).
•
The HDSC format is not supported.
Preparation
Copy all files from the directory
"Firmware\CoDeSys\NPLC C100 Factory Settings\SD Image"
including the file STARTUP.INI and the directory BACKUP and all
subdirectories onto an empty micro SD card to the card's root directory.
Procedure
1. Have the SD card ready with the copied image
2. Power down the PC the card is inserted. If used, switch off the external
power supply.
3. Insert the card into the SD card slot to the front of card
4. Re-Power the PC
°
The device loads the base firmware and indicates this by the following
states of the SYS LED: Fast change between green and yellow (for
appr. 8 s), then yellow on (for appr. 10 s), then off for a short moment
and finally it turns to green on.
°
The device then has factory settings.
5. Remove the SD card from the SD card slot