Technical Data
124/142
netPLC C100 | Startup Guide
DOC090701UM02EN | Revision 2 | English | 2009-10 | Released | Public
© Hilscher, 2009
17.2 Protocols
17.2.1 PROFIBUS
DP
Master
Parameter
Description
Maximum number of supported DPV0/DPV1
slaves
125
Maximum number of total cyclic input data
3584 bytes
Maximum number of total cyclic output data
3584 bytes
Maximum number of cyclic input data
244 bytes/slave
Maximum number of cyclic output data
244 bytes/slave
Configuration data
max. 244 bytes per slave
Parameterization data per slave
7 bytes/slave standard parameters
237 bytes/slave application specific parameters
Baud rate
Fixed values from 9,6 kBits/s to 12 MBit/s
Auto-detection mode is not supported.
Data transport layer
PROFIBUS FDL
Limitations
DP V1 services class 1 and 2 are not supported
DP V2 services are not implemented
Table 27: Technical Data PROFIBUS-DP Master Protocol