Technical Data
98/145
PC Cards cifX PCI, PCIe, Low Profile PCIe | Installation, Operation and Hardware Description
DOC120204UM36EN | Revision 36 | English | 2012-10 | Released | Public
© Hilscher, 2008-2012
10.1.2 CIFX
50-DP
Item
CIFX 50-DP
System Interface
(Bus Type)
PCI, according to [bus spec 1], (refer to section
Overview on the Pin
Assignment at the Bus
, page 95), 33 MHz, 32-Bit width for the data access to
the Dual-Port Memory (DPM), or IO-DMA (Direct Memory Access)
Dual-Port Memory Size
64 KByte
Function
Communication interface with PCI and PROFIBUS interface
Communication
Determined by the loaded firmware
Protocols
PROFIBUS DP Master, PROFIBUS DP Slave, PROFIBUS MPI Device
Processor
netX 100
LEDs
SYS, COM;
(refer also to chapter
LED Descriptions
, page 66).
Rotary Switch Slot Number
(Card ID)
To set the Slot Number (Card ID)
Configuration Software
SYCON.net (Master and Slave) or netX Configuration Tool (only Slave)
PROFIBUS Interface
DSub female Connector, 9 pin; Isolated RS-485 Interface;
(refer also to chapter
PROFIBUS Interface
page 88).
Supply Voltage
+3.3 V dc ±5 %/Typ. 650 mA
Dimensions (L x W x D)
Beginning with hardware revision 5: 120,0 x 86 x 18,5 mm;
[W = 86 mm, as with Rotary Switch Slot Number (Card ID)].
Operating Temperature
-20 °C ... +55 °C
Environment
The device must be used in a pollution degree 2 environment.
UL Certification
The device is UL 508 certified (UL-File No E221530).
Table 88: Technical Data CIFX 50-DP
10.1.3 CIFX
50-2DP
Item
CIFX 50-2DP
System Interface
(Bus Type)
PCI, according to [bus spec 1], (refer to section
Overview on the Pin
Assignment at the Bus
, page 95), 33 MHz, 32-Bit width for the data access to
the Dual-Port Memory (DPM), or IO-DMA (Direct Memory Access)
Dual-Port Memory Size
64 KByte
Function
Communication interface with PCI and 2 x PROFIBUS interface
Communication
Determined by the loaded firmware
Protocols
PROFIBUS DP Master, PROFIBUS DP Slave
Processor
netX 100
LEDs
SYS, COM1, COM2;
(refer also to chapter
LED Descriptions
, page 66).
Configuration Software
SYCON.net (Master and Slave) or netX Configuration Tool (only Slave)
PROFIBUS Interface
2 x DSub female Connector, 9 pin; Isolated RS-485 Interface;
(refer also to chapter
PROFIBUS Interface
page 88).
Supply Voltage
+3.3 V dc ±5 %/Typ. 750 mA
Dimensions (L x W x D)
120 x 94,5 x 18,5 mm
Operating Temperature
-20 °C ... +55 °C
Environment
The device must be used in a pollution degree 2 environment.
UL Certification
The device is UL 508 certified (UL-File No E221530).
Table 89: Technical Data CIFX 50-2DP