LED Descriptions
67/145
PC Cards cifX PCI, PCIe, Low Profile PCIe | Installation, Operation and Hardware Description
DOC120204UM36EN | Revision 36 | English | 2012-10 | Released | Public
© Hilscher, 2008-2012
8.2
Overview LEDs Fieldbus Systems
Label by Fieldbus System
LED
PROFIBUS DP
(1 Duo-
LED)
PROFIBUS DP
(1 Duo LE
D/ch
ann
el for
2-Ch
ann
el D
e
v
ices)
PROFIBUS MPI
(1 Duo LE
D)
CANope
n
(1 Duo LE
D)
Devic
e
Net
(1 Duo LE
D)
AS-Interface (Master)
(1 Duo LE
D/C
H
)
CC-L
in
k
(Slave)
(2 LEDs)
Co
mp
o
N
et (Slave)
(2 Duo LE
Ds
System Status
(yellow/green)
SYS SYS SYS SYS SYS SYS SYS SYS
COM COM0 COM CAN MNS CH0 L
RUN/ MS
Communica-
tion Status 0
(red/green)
Commu-
nication
Status
Commu-
nication
Status 0
Commu-
nication
Status
CANopen
Status
Module
Network
Status
Channel 0
L Run
Module
Status
- COM1 -
-
- CH1
L
ERR
NS
Communica-
tion Status 1
(red/green)
Commu-
nication
Status 1
Channel 1
L Error
Network
Status
Table 38: Overview LEDs by Fieldbus System
* Descriptions for 2-Communication LEDs of PROFIBUS DP Master and Slave devices as
well as of CANopen Master and Slave devices of earlier device revisions are included in
the user manual for PC cards cifX fieldbus up to manual rev. 23.
8.3 System
LED
The subsequent table describes the meaning of the system LED.
LED
Color
State
Meaning
Duo LED yellow/green
(yellow)
Static
Bootloader netX (= romloader) is waiting for second stage bootloader
(green/
yellow)
Blinking
green/
yellow
Second stage bootloader is waiting for firmware
(green)
On
Operating System running
SYS
(off)
Off
Power supply for the device is missing or hardware defect.
Table 39: System Status LED