LED Descriptions
73/145
PC Cards cifX PCI, PCIe, Low Profile PCIe | Installation, Operation and Hardware Description
DOC120204UM36EN | Revision 36 | English | 2012-10 | Released | Public
© Hilscher, 2008-2012
8.9
Powerlink Controlled Node/Slave
The subsequent table describes the meaning of the LEDs for the PC Card
cifX Real-Time Ethernet (Slave) when the firmware of the Powerlink
Controlled Node/Slave protocol is loaded to the device.
LED
Color
State
Meaning
Duo LED red/green
(off)
Off Slave
initializing
Flickering
Slave is in Basic Ethernet state
Single
Flash
Slave is in Pre-Operational 1
Double
Flash
Slave is in Pre-Operational 2
Triple Flash
Slave is in ReadyToOperate
On
Slave is Operational
BS
Name in
the device
drawing:
COM 0
(green)
Blinking
Slave is Stopped
Duo LED red/green
(off)
Off
Slave has no error
BE
Name in
the device
drawing:
COM 1
(red)
On
Slave has detected an error
LED green
(green)
On
Link
: A connection to the Ethernet exists
(green)
Flashing
Activity
: The device sends/receives Ethernet frames
L/A
/
RJ45
Ch0 & Ch1
(off)
Off
The device has no connection to the Ethernet
LED yellow
RJ45
Ch0 & Ch1
-
-
This LED is not used.
Table 47: LEDs Powerlink Controlled Node/Slave
LED State Definition for Powerlink Controlled Node/Slave for the
BS/BE LEDs
Indicator state
Definition
On
The indicator is constantly on.
Off
The indicator is constantly off.
Blinking
The indicator turns on and off with a frequency of approximately 2,5 Hz: on for approximately
200 ms, followed by off for 200 ms. Red and green LEDs shall be on alternately.
Flickering
The indicator turns on and off with a frequency of approximately 10 Hz: on for approximately 50
ms, followed by off for 50 ms. Red and green LEDs shall be on alternately.
Single Flash
The indicator shows one short flash (approximately 200 ms) followed by a long off phase
(approximately 1,000 ms).
Double Flash
The indicator shows a sequence of two short flashes (each approximately 200 ms), separated
by a short off phase (approximately 200 ms). The sequence is finished by a long off phase
(approximately 1,000 ms).
Triple Flash
The indicator shows a sequence of three short flashes (each approximately 200 ms), separated
by a short off phase (approximately 200 ms). The sequence is finished by a long off phase
(approximately 1,000 ms).
Table 48: LED State Definition for Powerlink Controlled Node/Slave for the BS/BE LEDs