www.hi-velocity.com
© 1995-2017 Energy Saving Products Ltd.
Display
Description
E00
Output Overcurrent/Short-Circuit
E01
DC Link Overvoltage
E02
DC Link Undervoltage
E04
Inverter Overtemperature
E05
Output Overload (I x t function)
E06
External Fault
E08
CPU Error (watchdog)
E09
Program Memory Error (checksum)
E24
Programming Error
E31
Keypad (HMI) Communication Fault 97
E41
Self-Diagnosis Error 97
Display
Description
rdy
Inverter is ready to be enabled
Sub
Power supply voltage is too low for the inverter operation
(undervoltage)
dcb
Inverter in DC braking mode
EPP
Inverter is loading factory setting
Fault Messages:
Other Messages:
WEG Variable Frequency Drive
-22-
Read-Only Parameters:
Parameter
Function
Range
Unit
Description
P002
Motor Frequency Output
0 to 66
Hz
Indicates the VFD Output Frequency in Hertz
P003
Motor Current Output
0 to 1.5 x Inom
A
Indicates the VFD Output Current in Amperes
P004
DC Link Voltage
0 to 524
V
Indicates the VFD DC Link Voltage in Volts
P007
Motor Voltage Output
0 to 240
V
Indicates the VFD Output Voltage in Volts
P008
Heatsink Temperature
25 to 110
ºC
Indicates the Heat Sink Temp in Celsius. The VFD
Overtemp Protection (E04) acts when Heatsink
Temperature reaches 103 ºC
P014
Last Fault
00 to 41
EXX
Indicates the Code of the last occurred Fault
P015
Second Fault Occurred
00 to 41
EXX
Indicates the Code of the 2nd last occurred Fault
P016
Third Fault Occurred
00 to 41
EXX
Indicates the Code of the 3rd last occurred Fault
Features:
•
Purposely oversized to ensure increased reliability and higher efficiencies at peak load
•
Features inherent with VFD allows for minimum power consumption at reduced loads (<100w average for constant fan
speed)
•
Error code read out allows for easy drive analysis in the event of a VFD fault
•
Programmable drive parameters allow for acceleration and deceleration speed to be adjusted if necessary
•
Digital display makes motor speed references simple
•
Large heat sink allows for excellent heat dissipation in high ambient environments
Function:
•
Takes single phase input (110v or 200-240v) and converts it to 3 phase output for the fan motor
• Fan speed is determined by the PSB circuit board which provides a 0-10vdc output to control the VFD
Module WIR
Hi-Velocity Wiring & Settings (2/10)
Module WIR Hi-Velocity Wiring and Settings (2/10)
The Hi-Velocity HE-Z Series Fan Coil utilizes a WEG Variable
Frequency Drive to run its 3-phase motor. The WEG VFD is a
reliable and robust motor control that will provide many years
of issue free operation.